Programming Options
38
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
4+2 Standard and 4+2 Express Formats
If '1, A or C' is entered for address 42, the following data is automatically programmed for the Secondary Phone num-
ber event codes. Enter a '0' for the data setting to disable the report.
TAB L E 3- 6 : Secondary Number Event Codes - 4+2 Standard and 4+2 Express
Address Description Setting
139 - 140 Secondary # General Alarm Code 11
141 - 142 Secondary # Zone/Point Alarm Code 00
143 - 144 Secondary # General Supervisory Code 81
145 - 146 Secondary # Zone/Point Supervisory Code 00
147 - 148 Secondary # General Fault Code F1
149 - 150 Secondary # AC Fault Code F6
151 - 152 Secondary # Zone/Point Fault Code 00
153 - 154 Secondary # Low Battery Fault Code F8
155 - 156 Secondary # Telco Primary Line Fault Code FA
157 - 158 Secondary # Telco Secondary Line Fault Code FB
159 - 160 Secondary # NAC Fault Code FC
161 - 162 Secondary # Communication Trouble Primary # Code FD
163 - 164 Secondary # Communication Trouble Secondary # Code FE
165 - 166 Secondary # 485 Communication Trouble Code FE
167 - 168 Secondary # System Off Normal Code FF
169 - 170 Secondary # UDACT-F Off Normal Code FF
171 - 172 Secondary # General Alarm Restore Code E1
173 - 174 Secondary # Zone/Point Alarm Restore Code 00
175 - 176 Secondary # General Supervisory Restore Code E2
177 - 178 Secondary # Zone/Point Supervisory Restore Code 00
179 - 180 Secondary # General Fault Restore Code E3
181 - 182 Secondary # AC Fault Restore Code E6
183 - 184 Secondary # Zone/Point Fault Restore Code 00
185 - 186 Secondary # Low Battery Fault Restore Code E8
187 - 188 Secondary # Telco Primary Line Fault Restore Code EA
189 - 190 Secondary # Telco Secondary Line Fault Restore Code EB
191 - 192 Secondary # NAC Fault Restore Code EC
193 - 194 Secondary # Communication Trouble Primary Number Restore Code ED
195 - 196 Secondary # Communication Trouble Secondary Number Restore Code EE
197 - 198 Secondary # 485 Communication Trouble Restore Code EE
199 - 200 Secondary # System Off Normal Restore Code EF
201 - 202 Secondary # UDACT-F Off Normal Restore Code EF
203 - 204 Secondary # System 24 Hour Test 99
205 - 206 Secondary # System 24 Hour Test with Active Event 91
207 - 208 Secondary # Manual Test 92
Note: Zero entries prevent the transmission of the report to the Central Station

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fire-Lite UDACT-F and is the answer not in the manual?

Fire-Lite UDACT-F Specifications

General IconGeneral
BrandFire-Lite
ModelUDACT-F
CategorySecurity System
LanguageEnglish

Related product manuals