EasyManua.ls Logo

FirePro FPX103C - DIP Switch Settings and Configuration; Alarm Option Selection (DIP Switch 4)

Default Icon
10 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ELECTRICAL SPECIFICATION (at 24VDC supply unless otherwise stated):
Power Supply
Operating Voltage
11 to 32V DC
Quescent Current Ign Off
8.5mA Typ (excluding external load currents)
Ign On
16mA Typ (excluding external load currents)
Maximum Alarm Current
Draw
100mA (excluding external load currents)
Max current draw
3A (including extinguisher operate current)
Parked current draw
8.5mA Typ
Suppressor Activation
Discharge Current
1A to 4A depending on voltage and number of
suppressors (StatX = 1.8 Ohms nominal each unit)
Up to 2 units on 12V, 4 units max on 24V
Connect in series with bi-directional catch diodes
across each element (see manual).
Current/Time Limit
Output is Vin via switch with 6 Ohms in series.
Constant I2T limit = 9 Amp2*Seconds
Monitoring current
<4mA, Fault if loop R>300, 12Vmax o/c voltage
AuxIn (Override key)
Monitoring current
1.2mA Nominal
Sense Logic
Norm S/C, >1K active typ.
Sensor Loop Inputs 1+2
Max Output voltage
12VDC regulated, filtered and transient protected
Output current limit
25mA per loop
Alarm condition threshold
<700 Ohms Nominal
Fault condition threshold
Approximately 20K Ohms
End Of Line Resistor
10K Ohms
Fault monitoring
Open circuit or ground fault = fault indication
Alarm Output
Relay Contacts
2A @ VinDC (Vin thru NO relay circuit)
VFC Output
Relay Contacts (volt free)
2A @ 24VDC (relay changeover circuit)
Mechanical
Dimensions
H=82mm * W=83mm * D=25mm
Mounting
75mm diameter round hole, retained by four #6*25
self tapping screws
Connections
Via 3 * 6 way terminal block accepting <1mm
2
wires with ferrules
DIP SWITCH SETTINGS (Black = switch tab)
DIP switches 1.2.3 set a delay time between shutdown (VFC) and subsequent
extinguisher automatic activation. Delay can be set 0 to 30 seconds in 5 second steps.
Manual only mode can be set with ON.ON.ON.OPT
DIP switch 4 defines critical alarm OPTion.
The default setting is OFF which requires 2 loops to be in alarm (OPT=“double knock”)
before shutdown and time delayed extinguisher activation.
Moving to ON position requires only one loop to be in alarm (OPT=“single knock”)
before shutdown and time delayed extinguisher activation.
Note that the unit dispenses activation delay following depowering of ignition input.
The instant mode is indicated by flashing green PWR LED which gives double flash
whilst moving through the delay and single flash on reaching zero delay instant mode.