Fan/Engine “Spindown” delay time before automatic release.
Note: Spindown delay only when ignition is ON
OFF.OFF.OFF.OPT 0 Sec = Immediate
ON.OFF.OFF.OPT 5 Sec
OFF.ON.OFF.OPT 10 Sec
ON.ON.OFF.OPT 15 Sec
OFF.OFF.ON.OPT 20 Sec
ON.OFF.ON.OPT 25 Sec
OFF.ON.ON.OPT 30 Sec
ON.ON.ON.OPT No Automatic Operation
Installation Notes:
Ensure that Linear Heat Detectors are suitably mounted for the vehicle vibration levels.
Front of panel is splash proof but it must be located to prevent excessive moisture or water getting to
the unit, especially the rear connections.
Locate to avoid excessive direct solar exposure.
WARNING! (And some common sense…..) Refer to the installation manual.
System installation must be verified by a competent technician familiar with regulations governing such
installations.
Do not install in Engine, bilge, fuel or gas storage compartments (see RCD and ISO9094).
In the event of an alarm shutdown the engines and ventilation immediately.
The cause of the activation must be found and corrected before restarting.
DO NOT PROCEED TO OVERRIDE UNLESS IT HAS BEEN DETERMINED SAFE TO DO SO.