SEPARATE SENSORS TO DETECT SMOKE AND CO;
THE TWO ALARM SYSTEMS WORK INDEPENDENTLY
SEALED-IN LITHIUM BATTERY — SEALED-IN LITHIUM POWER SUPPLY; NO
BATTERY REPLACEMENT REQUIRED OVER THE 10 YEAR LIFE OF THE ALARM.
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Combination Carbon Monoxide & Smoke
Alarm’s operation. If you are installing this Alarm for use by others, you must leave
this manual—or a copy of it—with the end user.
PARA EL MANUAL DEL USUARIO EN ESPAÑOL,
POR FAVOR VISITE WWW.FIRSTALERT.COM.
USER’S MANUAL
COMBINATION CARBON MONOXIDE & SMOKE ALARM
RECOMMENDED PLACEMENT
• When installing on the wall, the top edge of Smoke
Alarms should be placed between 4 inches (102 mm) and
12 inches (305 mm) from the wall/ceiling line.
• When installing on the ceiling, place the alarm as close to
the center as possible.
• In either case, install at least 4 inches (102 mm) from
where the wall and ceiling meet. See “Avoiding Dead Air
Spaces” for more information.
NOTE: For any location, make sure no door or other
obstruction could keep carbon monoxide or smoke from
reaching the Alarm.
Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close
to each sleeping area as possible. For more security, put
one unit in each room. Many older mobile homes (especially
those built before 1978) have little or no insulation. If your
mobile home is not well insulated, or if you are unsure of
the amount of insulation, it is important to install units on inside walls only.
___________________________________________________________________________________________________________________________
WHERE THIS ALARM SHOULD NOT BE INSTALLED
DO NOT LOCATE THIS SMOKE/CO ALARM:
• In garages, furnace rooms, crawl spaces and unfinished attics. Avoid extremely dusty, dirty or greasy areas.
• Where combustion particles are produced. Combustion particles form when something burns. Areas to avoid include poorly ventilated kitchens, garages, and
furnace rooms. Keep units at least 20 feet (6 meters) from the sources of combustion particles (stove, furnace, water heater, space heater) if possible. In areas
where a 20-foot (6 meter) distance is not possible – in modular, mobile, or smaller homes, for example – it is recommended the Smoke Alarm be placed as far
from these fuel-burning sources as possible. The placement recommendations are intended to keep these Alarms at a reasonable distance from a fuel-burning
source, and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is placed directly next to a fuel-burning source. Ventilate these areas
as much as possible.
• Within 5 feet (1.5 meters) of any cooking appliance. In air streams near kitchens. Air currents can draw cooking smoke into the smoke sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 10 feet (3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room, utility room, or
other source of high humidity.
• In direct sunlight.
• In turbulent air, like near ceiling fans or open windows. Blowing air may prevent CO or smoke from reaching the sensors.
• In areas where temperature is colder than 40˚ F (4.4˚ C) or hotter than 100˚F (37.8˚ C). These areas include non-airconditioned crawl spaces, unfinished attics,
uninsulated or poorly insulated ceilings, porches, and garages.
• In insect infested areas. Insects can clog the openings to the sensing chamber.
• Less than 12 inches (305 mm) away from fluorescent lights. Electrical “noise” can interfere with the sensor.
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm. To avoid dead air spaces, follow installation recommendations below.
On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible. If this is not possible, install the Smoke/CO Alarm at least 4 inches (102 mm)
from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke/CO Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm) from
the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally. Additional
Smoke/CO Alarms may be required depending on the length, angle, etc. of the ceiling’s slope. Refer to NFPA 72 for details on requirements for sloped or peaked
ceilings.
WEEKLY TESTING
• NEVER use an open flame of any kind to test this unit. You might accidentally damage or set fire to the unit or to your home. The built-in test switch
accurately tests the unit’s operation as required by Underwriters Laboratories, Inc. (UL). NEVER use vehicle exhaust! Exhaust may cause permanent
damage and voids your warranty.
• DO NOT stand close to the alarm when the horn is sounding. Exposure at close range may be harmful to your hearing. When testing, step away when
horn starts sounding.
It is important to test this unit every week to make sure it is working properly.
Using the test button is the recommended way to test this Smoke/CO Alarm.
You can test this Smoke/CO Alarm: Press and hold the Test/Silence button 3-5 seconds until unit starts to alarm. During testing, you will see and hear the
following sequence:
• The Horn will sound 3 beeps, pause, 3 beeps. The LED flashes Red.
• Next the Horn will sound 4 beeps, pause, 4 beeps. The LED flashes Red.
If the unit does not alarm, make sure the batteries are correctly installed, and test again. If the unit still does not alarm, replace it immediately.
REGULAR MAINTENANCE
This unit has been designed to be as maintenance free as possible, but there are a few simple things you must do to keep it working properly.
• Test it at least once a week.
• Clean the Smoke/CO Alarm at least once a month; gently vacuum the outside of the Smoke/CO Alarm using your household vacuum’s soft brush attachment. A can
of clean compressed air (sold at computer or office supply stores) may also be used. Follow manufacturer instructions for use. Test the Smoke/CO Alarm. Never use
water, cleaners or solvents since they may damage the unit.
• If the Smoke/CO Alarm becomes contaminated by excessive dirt, dust and/or grime, and cannot be cleaned to avoid unwanted alarms, replace the unit
immediately.
• Relocate the unit if it sounds frequent unwanted alarms. See “Where This Alarm Should Not Be Installed” for details.
Actual battery service life depends on the Smoke/CO Alarm and the environment in which it is installed. Regardless of the manufacturer’s suggested battery life, you
MUST replace the Alarm immediately once the unit starts “chirping” (the “low battery warning”).
CONFORMS TO
UL STD 217 AND
UL STD 2034
Model PC910
INTRODUCTION
All First Alert® Smoke Alarms conform to regulatory requirements, including UL217 and are designed to detect particles of combustion. Smoke particles
of varying number and size are produced in all fires.
Ionization technology is generally more sensitive than photoelectric technology at detecting small particles, which tend to be produced in greater amounts by
flaming fires, which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a wastebasket, or a
grease fire in the kitchen.
Photoelectric technology is generally more sensitive than ionization technology at detecting large particles, which tend to be produced in greater amounts by
smoldering fires, which may smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each level and in every bedroom of your home.
___________________________________________________________________________________________________________________________
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking materials properly. Never smoke in bed. 2) Keep matches or lighters away from children; 3)
Store flammable materials in proper containers; 4) Keep electrical appliances in good condition and don’t overload electrical circuits; 5) Keep stoves, barbecue grills,
fireplaces and chimneys grease- and debris-free; 6) Never leave anything cooking on the stove unattended; 7) Keep portable heaters and open flames, like candles,
away from flammable materials; 8) Don’t let rubbish accumulate. Keep alarms clean, and test them weekly. Replace alarms immediately if they are not working
properly. Smoke Alarms that do not work cannot alert you to a fire. Keep at least one working fire extinguisher on every floor, and an additional one in the kitchen.
Have fire escape ladders or other reliable means of escape from an upper floor in case stairs are blocked.
INSTALLATION
WHERE TO INSTALL THIS ALARM
MINIMUM COVERAGE FOR SMOKE ALARMS, as recommended by the National Fire Protection Association (NFPA), is one Smoke Alarm on every floor, in every
sleeping area, and in every bedroom (See “Regulatory Information For Smoke Alarms” for details on the NFPA recommendations). For CO Alarms, the National
Fire Protection Association (NFPA) recommends that a CO Alarm should be centrally located outside of each separate sleeping area in the immediate vicinity of the
bedrooms. For added protection, install additional CO Alarms in each separate bedroom, and on every level of your home. NOTE: For added protection, install an
additional Smoke/CO Alarm at least 15 feet (4.6 meters) away from the furnace or fuel burning heat source where possible. In smaller homes or in manufactured
homes where this distance cannot be maintained, install the Alarm as far away as possible from the furnace or other fuel burning source. Installing the Alarm closer
than 15 feet (4.6 meters) will not harm the Alarm, but may increase the frequency of unwanted alarms.
In general, install combination Smoke and Carbon Monoxide Alarms:
• On every level of your home, including finished attics and basements.
• Inside every bedroom, especially if people sleep with the door partly or completely closed.
• In the hall near every sleeping area. If your home has multiple sleeping areas, install a unit in each. If a hall is more than 40 feet (12 meters) long, install a unit at
each end.
• At the top of first-to-second floor stairs.
• At the bottom of the basement stairs.
• For additional coverage, install Alarms in all rooms, halls, and storage areas,
where temperatures normally remain between 40˚ F and 100˚ F (4.4˚ C and 37.8˚ C).
IF YOUR SMOKE/CO ALARM SOUNDS
WHAT TO DO FIRST–IDENTIFY THE TYPE OF ALARM
“ALARM-MOVE TO FRESH AIR”
If you hear the CO alarm horn and the CO red light is flashing,
move everyone to a source of fresh air.
DO NOT remove the batteries!
Type of Alarm What You See and Hear
Carbon Monoxide (CO)
CO LED: Flashes Red
Horn: 4 beeps, pause, 4 beeps, pause
Smoke
Smoke LED: Flashes Red
Horn: 3 beeps, pause, 3 beeps, pause
SUGGESTED AREAS FOR INSTALLING
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
SMOKE ALARM WITH
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION
SMOKE/CO ALARMS
SMOKE ALARMS
KEY:
Suggested locations are based on
NFPA recommendations (NFPA 72
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always
refer to national and local codes
before beginning any installation.
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
© 2015 BRK Brands, Inc. All rights reserved. Distributed by BRK Brands, Inc. First Alert® is registered trademark of The First Alert Trust
3901 Liberty Street Road, Aurora, IL 60504-8122 Consumer Affairs: (800) 323-9005 • www.firstalert.com www.brkelectronics.com • 2/15
Printed in Mexico • M08-0407-009
Y
Installed on Replace by
HOW TO INSTALL THIS ALARM
This combination Smoke/CO Alarm was designed to be mounted on the ceiling or wall. It is not a tabletop device. You must install this device on the ceiling or
wall as outlined below. Read “Where To Install This Alarm” before starting.
• Do not connect this unit to any other alarm or auxiliary device. It is a single-station unit that cannot be linked to other devices. Connecting anything
else to this unit may prevent it from working properly.
• Do not install this unit over an electrical junction box. Air currents around junction boxes can prevent smoke from reaching the sensing chamber and
prevent the unit from alarming. Only AC powered units are intended for installation over junction boxes..
TOOLS YOU WILL NEED:
THIS UNIT IS DESIGNED TO BE MOUNTED ON THE CEILING, OR ON THE WALL IF NECESSARY.
• Pencil
• Drill with 3/16” (5 mm) drill bit
• Standard flathead screwdriver
• Hammer
THE PARTS OF THIS
SMOKE/CO ALARM
1 Test/Silence Button
2 Power/Smoke Alarm and
CO Alarm LED
1 Mounting bracket
2 Mounting slots
FOLLOW THESE SIMPLE STEPS
1. Turn alarm upside down so the circular shape is located in the upper left corner of the alarm.
2. If mounting bracket is attached to alarm, lift to separate it from the base.
3. Hold the mounting bracket against the ceiling
(or wall) so the arrow located on the mounting
plate is pointing to the left. (The circular shape
will now be in upper right-hand corner). Trace
around the insides of the mounting slots.
4. Put the unit where it won’t get covered with
dust when you drill the mounting holes.
5. Using a 3/16” (5 mm) drill bit, drill a hole
through the center of the oval outlines you
traced in step #3.
6. Insert the plastic screw anchors (in the plastic
bag with screws) into the holes. Tap the screw anchors gently
with a hammer, if necessary, until they are flush with the ceiling
or wall.
7. Line the mounting bracket up over the plastic screw anchors.
Screw the mounting bracket to the ceiling or wall through the
mounting slots using the two screws provided.
8. Activate the battery. Move the activation switch to “ON”
position against tab stop. Unit will not mount on mounting
bracket unless activated. Once unit is activated, it cannot be
turned off.
NOTE: After you activate the battery, the power indicator light
may flash. (If the unit alarms, the light will blink rapidly, and
the horn will repeatedly sound 3 beeps, pause, 3 beeps.)
9. Attach the Smoke/CO Alarm to the mounting bracket. Hold
alarm as shown in diagram. Place alarm on mounting bracket
and slide to the right until locked into place.
NOTE: Once the Smoke/CO Alarm is snapped onto the
mounting bracket,
you can rotate the Smoke/CO Alarm to adjust the alignment.
10. Test the Smoke/CO Alarm. See “Weekly Testing.”
11. To Permanently Deactivate the Smoke/CO Alarm. After
10 years of operation or Low Battery warning, deactivate the
Alarm: Insert a tool below edge where shown and break tab.
Then slide activation switch to DEACTIVATE mode.
NOTE: At end of life or low battery indication (chirp): unit
must be put in to deactivation mode to deactivate remaining
stored energy in battery. Unit will no longer function once
put into this mode. Unit will resist re-mounting.
NOTE: Be sure to mount the product in the orientation
specified in the next steps as this provides the most
stability for mounting the product to the wall or ceiling.
ON DEACTIVATE
SEPARATE SENSORS TO DETECT SMOKE AND CO;
THE TWO ALARM SYSTEMS WORK INDEPENDENTLY
SEALED-IN LITHIUM BATTERY — SEALED-IN LITHIUM POWER SUPPLY; NO
BATTERY REPLACEMENT REQUIRED OVER THE 10 YEAR LIFE OF THE ALARM.
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Combination Carbon Monoxide & Smoke
Alarm’s operation. If you are installing this Alarm for use by others, you must leave
this manual—or a copy of it—with the end user.
PARA EL MANUAL DEL USUARIO EN ESPAÑOL,
POR FAVOR VISITE WWW.FIRSTALERT.COM.
USER’S MANUAL
COMBINATION CARBON MONOXIDE & SMOKE ALARM
RECOMMENDED PLACEMENT
• When installing on the wall, the top edge of Smoke
Alarms should be placed between 4 inches (102 mm) and
12 inches (305 mm) from the wall/ceiling line.
• When installing on the ceiling, place the alarm as close to
the center as possible.
• In either case, install at least 4 inches (102 mm) from
where the wall and ceiling meet. See “Avoiding Dead Air
Spaces” for more information.
NOTE: For any location, make sure no door or other
obstruction could keep carbon monoxide or smoke from
reaching the Alarm.
Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close
to each sleeping area as possible. For more security, put
one unit in each room. Many older mobile homes (especially
those built before 1978) have little or no insulation. If your
mobile home is not well insulated, or if you are unsure of
the amount of insulation, it is important to install units on inside walls only.
___________________________________________________________________________________________________________________________
WHERE THIS ALARM SHOULD NOT BE INSTALLED
DO NOT LOCATE THIS SMOKE/CO ALARM:
• In garages, furnace rooms, crawl spaces and unfinished attics. Avoid extremely dusty, dirty or greasy areas.
• Where combustion particles are produced. Combustion particles form when something burns. Areas to avoid include poorly ventilated kitchens, garages, and
furnace rooms. Keep units at least 20 feet (6 meters) from the sources of combustion particles (stove, furnace, water heater, space heater) if possible. In areas
where a 20-foot (6 meter) distance is not possible – in modular, mobile, or smaller homes, for example – it is recommended the Smoke Alarm be placed as far
from these fuel-burning sources as possible. The placement recommendations are intended to keep these Alarms at a reasonable distance from a fuel-burning
source, and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is placed directly next to a fuel-burning source. Ventilate these areas
as much as possible.
• Within 5 feet (1.5 meters) of any cooking appliance. In air streams near kitchens. Air currents can draw cooking smoke into the smoke sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 10 feet (3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room, utility room, or
other source of high humidity.
• In direct sunlight.
• In turbulent air, like near ceiling fans or open windows. Blowing air may prevent CO or smoke from reaching the sensors.
• In areas where temperature is colder than 40˚ F (4.4˚ C) or hotter than 100˚F (37.8˚ C). These areas include non-airconditioned crawl spaces, unfinished attics,
uninsulated or poorly insulated ceilings, porches, and garages.
• In insect infested areas. Insects can clog the openings to the sensing chamber.
• Less than 12 inches (305 mm) away from fluorescent lights. Electrical “noise” can interfere with the sensor.
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm. To avoid dead air spaces, follow installation recommendations below.
On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible. If this is not possible, install the Smoke/CO Alarm at least 4 inches (102 mm)
from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke/CO Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm) from
the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally. Additional
Smoke/CO Alarms may be required depending on the length, angle, etc. of the ceiling’s slope. Refer to NFPA 72 for details on requirements for sloped or peaked
ceilings.
WEEKLY TESTING
• NEVER use an open flame of any kind to test this unit. You might accidentally damage or set fire to the unit or to your home. The built-in test switch
accurately tests the unit’s operation as required by Underwriters Laboratories, Inc. (UL). NEVER use vehicle exhaust! Exhaust may cause permanent
damage and voids your warranty.
• DO NOT stand close to the alarm when the horn is sounding. Exposure at close range may be harmful to your hearing. When testing, step away when
horn starts sounding.
It is important to test this unit every week to make sure it is working properly.
Using the test button is the recommended way to test this Smoke/CO Alarm.
You can test this Smoke/CO Alarm: Press and hold the Test/Silence button 3-5 seconds until unit starts to alarm. During testing, you will see and hear the
following sequence:
• The Horn will sound 3 beeps, pause, 3 beeps. The LED flashes Red.
• Next the Horn will sound 4 beeps, pause, 4 beeps. The LED flashes Red.
If the unit does not alarm, make sure the batteries are correctly installed, and test again. If the unit still does not alarm, replace it immediately.
REGULAR MAINTENANCE
This unit has been designed to be as maintenance free as possible, but there are a few simple things you must do to keep it working properly.
• Test it at least once a week.
• Clean the Smoke/CO Alarm at least once a month; gently vacuum the outside of the Smoke/CO Alarm using your household vacuum’s soft brush attachment. A can
of clean compressed air (sold at computer or office supply stores) may also be used. Follow manufacturer instructions for use. Test the Smoke/CO Alarm. Never use
water, cleaners or solvents since they may damage the unit.
• If the Smoke/CO Alarm becomes contaminated by excessive dirt, dust and/or grime, and cannot be cleaned to avoid unwanted alarms, replace the unit
immediately.
• Relocate the unit if it sounds frequent unwanted alarms. See “Where This Alarm Should Not Be Installed” for details.
Actual battery service life depends on the Smoke/CO Alarm and the environment in which it is installed. Regardless of the manufacturer’s suggested battery life, you
MUST replace the Alarm immediately once the unit starts “chirping” (the “low battery warning”).
CONFORMS TO
UL STD 217 AND
UL STD 2034
Model PC910
INTRODUCTION
All First Alert® Smoke Alarms conform to regulatory requirements, including UL217 and are designed to detect particles of combustion. Smoke particles
of varying number and size are produced in all fires.
Ionization technology is generally more sensitive than photoelectric technology at detecting small particles, which tend to be produced in greater amounts by
flaming fires, which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a wastebasket, or a
grease fire in the kitchen.
Photoelectric technology is generally more sensitive than ionization technology at detecting large particles, which tend to be produced in greater amounts by
smoldering fires, which may smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each level and in every bedroom of your home.
___________________________________________________________________________________________________________________________
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking materials properly. Never smoke in bed. 2) Keep matches or lighters away from children; 3)
Store flammable materials in proper containers; 4) Keep electrical appliances in good condition and don’t overload electrical circuits; 5) Keep stoves, barbecue grills,
fireplaces and chimneys grease- and debris-free; 6) Never leave anything cooking on the stove unattended; 7) Keep portable heaters and open flames, like candles,
away from flammable materials; 8) Don’t let rubbish accumulate. Keep alarms clean, and test them weekly. Replace alarms immediately if they are not working
properly. Smoke Alarms that do not work cannot alert you to a fire. Keep at least one working fire extinguisher on every floor, and an additional one in the kitchen.
Have fire escape ladders or other reliable means of escape from an upper floor in case stairs are blocked.
INSTALLATION
WHERE TO INSTALL THIS ALARM
MINIMUM COVERAGE FOR SMOKE ALARMS, as recommended by the National Fire Protection Association (NFPA), is one Smoke Alarm on every floor, in every
sleeping area, and in every bedroom (See “Regulatory Information For Smoke Alarms” for details on the NFPA recommendations). For CO Alarms, the National
Fire Protection Association (NFPA) recommends that a CO Alarm should be centrally located outside of each separate sleeping area in the immediate vicinity of the
bedrooms. For added protection, install additional CO Alarms in each separate bedroom, and on every level of your home. NOTE: For added protection, install an
additional Smoke/CO Alarm at least 15 feet (4.6 meters) away from the furnace or fuel burning heat source where possible. In smaller homes or in manufactured
homes where this distance cannot be maintained, install the Alarm as far away as possible from the furnace or other fuel burning source. Installing the Alarm closer
than 15 feet (4.6 meters) will not harm the Alarm, but may increase the frequency of unwanted alarms.
In general, install combination Smoke and Carbon Monoxide Alarms:
• On every level of your home, including finished attics and basements.
• Inside every bedroom, especially if people sleep with the door partly or completely closed.
• In the hall near every sleeping area. If your home has multiple sleeping areas, install a unit in each. If a hall is more than 40 feet (12 meters) long, install a unit at
each end.
• At the top of first-to-second floor stairs.
• At the bottom of the basement stairs.
• For additional coverage, install Alarms in all rooms, halls, and storage areas,
where temperatures normally remain between 40˚ F and 100˚ F (4.4˚ C and 37.8˚ C).
IF YOUR SMOKE/CO ALARM SOUNDS
WHAT TO DO FIRST–IDENTIFY THE TYPE OF ALARM
“ALARM-MOVE TO FRESH AIR”
If you hear the CO alarm horn and the CO red light is flashing,
move everyone to a source of fresh air.
DO NOT remove the batteries!
Type of Alarm What You See and Hear
Carbon Monoxide (CO)
CO LED: Flashes Red
Horn: 4 beeps, pause, 4 beeps, pause
Smoke
Smoke LED: Flashes Red
Horn: 3 beeps, pause, 3 beeps, pause
SUGGESTED AREAS FOR INSTALLING
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
SMOKE ALARM WITH
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION
SMOKE/CO ALARMS
SMOKE ALARMS
KEY:
Suggested locations are based on
NFPA recommendations (NFPA 72
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always
refer to national and local codes
before beginning any installation.
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
© 2015 BRK Brands, Inc. All rights reserved. Distributed by BRK Brands, Inc. First Alert® is registered trademark of The First Alert Trust
3901 Liberty Street Road, Aurora, IL 60504-8122 Consumer Affairs: (800) 323-9005 • www.firstalert.com www.brkelectronics.com • 2/15
Printed in Mexico • M08-0407-009
Y
Installed on Replace by
HOW TO INSTALL THIS ALARM
This combination Smoke/CO Alarm was designed to be mounted on the ceiling or wall. It is not a tabletop device. You must install this device on the ceiling or
wall as outlined below. Read “Where To Install This Alarm” before starting.
• Do not connect this unit to any other alarm or auxiliary device. It is a single-station unit that cannot be linked to other devices. Connecting anything
else to this unit may prevent it from working properly.
• Do not install this unit over an electrical junction box. Air currents around junction boxes can prevent smoke from reaching the sensing chamber and
prevent the unit from alarming. Only AC powered units are intended for installation over junction boxes..
TOOLS YOU WILL NEED:
THIS UNIT IS DESIGNED TO BE MOUNTED ON THE CEILING, OR ON THE WALL IF NECESSARY.
• Pencil
• Drill with 3/16” (5 mm) drill bit
• Standard flathead screwdriver
• Hammer
THE PARTS OF THIS
SMOKE/CO ALARM
1 Test/Silence Button
2 Power/Smoke Alarm and
CO Alarm LED
1 Mounting bracket
2 Mounting slots
FOLLOW THESE SIMPLE STEPS
1. Turn alarm upside down so the circular shape is located in the upper left corner of the alarm.
2. If mounting bracket is attached to alarm, lift to separate it from the base.
3. Hold the mounting bracket against the ceiling
(or wall) so the arrow located on the mounting
plate is pointing to the left. (The circular shape
will now be in upper right-hand corner). Trace
around the insides of the mounting slots.
4. Put the unit where it won’t get covered with
dust when you drill the mounting holes.
5. Using a 3/16” (5 mm) drill bit, drill a hole
through the center of the oval outlines you
traced in step #3.
6. Insert the plastic screw anchors (in the plastic
bag with screws) into the holes. Tap the screw anchors gently
with a hammer, if necessary, until they are flush with the ceiling
or wall.
7. Line the mounting bracket up over the plastic screw anchors.
Screw the mounting bracket to the ceiling or wall through the
mounting slots using the two screws provided.
8. Activate the battery. Move the activation switch to “ON”
position against tab stop. Unit will not mount on mounting
bracket unless activated. Once unit is activated, it cannot be
turned off.
NOTE: After you activate the battery, the power indicator light
may flash. (If the unit alarms, the light will blink rapidly, and
the horn will repeatedly sound 3 beeps, pause, 3 beeps.)
9. Attach the Smoke/CO Alarm to the mounting bracket. Hold
alarm as shown in diagram. Place alarm on mounting bracket
and slide to the right until locked into place.
NOTE: Once the Smoke/CO Alarm is snapped onto the
mounting bracket,
you can rotate the Smoke/CO Alarm to adjust the alignment.
10. Test the Smoke/CO Alarm. See “Weekly Testing.”
11. To Permanently Deactivate the Smoke/CO Alarm. After
10 years of operation or Low Battery warning, deactivate the
Alarm: Insert a tool below edge where shown and break tab.
Then slide activation switch to DEACTIVATE mode.
NOTE: At end of life or low battery indication (chirp): unit
must be put in to deactivation mode to deactivate remaining
stored energy in battery. Unit will no longer function once
put into this mode. Unit will resist re-mounting.
NOTE: Be sure to mount the product in the orientation
specified in the next steps as this provides the most
stability for mounting the product to the wall or ceiling.
ON DEACTIVATE
SEPARATE SENSORS TO DETECT SMOKE AND CO;
THE TWO ALARM SYSTEMS WORK INDEPENDENTLY
SEALED-IN LITHIUM BATTERY — SEALED-IN LITHIUM POWER SUPPLY; NO
BATTERY REPLACEMENT REQUIRED OVER THE 10 YEAR LIFE OF THE ALARM.
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Combination Carbon Monoxide & Smoke
Alarm’s operation. If you are installing this Alarm for use by others, you must leave
this manual—or a copy of it—with the end user.
PARA EL MANUAL DEL USUARIO EN ESPAÑOL,
POR FAVOR VISITE WWW.FIRSTALERT.COM.
USER’S MANUAL
COMBINATION CARBON MONOXIDE & SMOKE ALARM
RECOMMENDED PLACEMENT
• When installing on the wall, the top edge of Smoke
Alarms should be placed between 4 inches (102 mm) and
12 inches (305 mm) from the wall/ceiling line.
• When installing on the ceiling, place the alarm as close to
the center as possible.
• In either case, install at least 4 inches (102 mm) from
where the wall and ceiling meet. See “Avoiding Dead Air
Spaces” for more information.
NOTE: For any location, make sure no door or other
obstruction could keep carbon monoxide or smoke from
reaching the Alarm.
Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close
to each sleeping area as possible. For more security, put
one unit in each room. Many older mobile homes (especially
those built before 1978) have little or no insulation. If your
mobile home is not well insulated, or if you are unsure of
the amount of insulation, it is important to install units on inside walls only.
___________________________________________________________________________________________________________________________
WHERE THIS ALARM SHOULD NOT BE INSTALLED
DO NOT LOCATE THIS SMOKE/CO ALARM:
• In garages, furnace rooms, crawl spaces and unfinished attics. Avoid extremely dusty, dirty or greasy areas.
• Where combustion particles are produced. Combustion particles form when something burns. Areas to avoid include poorly ventilated kitchens, garages, and
furnace rooms. Keep units at least 20 feet (6 meters) from the sources of combustion particles (stove, furnace, water heater, space heater) if possible. In areas
where a 20-foot (6 meter) distance is not possible – in modular, mobile, or smaller homes, for example – it is recommended the Smoke Alarm be placed as far
from these fuel-burning sources as possible. The placement recommendations are intended to keep these Alarms at a reasonable distance from a fuel-burning
source, and thus reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is placed directly next to a fuel-burning source. Ventilate these areas
as much as possible.
• Within 5 feet (1.5 meters) of any cooking appliance. In air streams near kitchens. Air currents can draw cooking smoke into the smoke sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 10 feet (3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room, utility room, or
other source of high humidity.
• In direct sunlight.
• In turbulent air, like near ceiling fans or open windows. Blowing air may prevent CO or smoke from reaching the sensors.
• In areas where temperature is colder than 40˚ F (4.4˚ C) or hotter than 100˚F (37.8˚ C). These areas include non-airconditioned crawl spaces, unfinished attics,
uninsulated or poorly insulated ceilings, porches, and garages.
• In insect infested areas. Insects can clog the openings to the sensing chamber.
• Less than 12 inches (305 mm) away from fluorescent lights. Electrical “noise” can interfere with the sensor.
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm. To avoid dead air spaces, follow installation recommendations below.
On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as possible. If this is not possible, install the Smoke/CO Alarm at least 4 inches (102 mm)
from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of Smoke/CO Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm) from
the wall/ceiling line, below typical “dead air” spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally. Additional
Smoke/CO Alarms may be required depending on the length, angle, etc. of the ceiling’s slope. Refer to NFPA 72 for details on requirements for sloped or peaked
ceilings.
WEEKLY TESTING
• NEVER use an open flame of any kind to test this unit. You might accidentally damage or set fire to the unit or to your home. The built-in test switch
accurately tests the unit’s operation as required by Underwriters Laboratories, Inc. (UL). NEVER use vehicle exhaust! Exhaust may cause permanent
damage and voids your warranty.
• DO NOT stand close to the alarm when the horn is sounding. Exposure at close range may be harmful to your hearing. When testing, step away when
horn starts sounding.
It is important to test this unit every week to make sure it is working properly.
Using the test button is the recommended way to test this Smoke/CO Alarm.
You can test this Smoke/CO Alarm: Press and hold the Test/Silence button 3-5 seconds until unit starts to alarm. During testing, you will see and hear the
following sequence:
• The Horn will sound 3 beeps, pause, 3 beeps. The LED flashes Red.
• Next the Horn will sound 4 beeps, pause, 4 beeps. The LED flashes Red.
If the unit does not alarm, make sure the batteries are correctly installed, and test again. If the unit still does not alarm, replace it immediately.
REGULAR MAINTENANCE
This unit has been designed to be as maintenance free as possible, but there are a few simple things you must do to keep it working properly.
• Test it at least once a week.
• Clean the Smoke/CO Alarm at least once a month; gently vacuum the outside of the Smoke/CO Alarm using your household vacuum’s soft brush attachment. A can
of clean compressed air (sold at computer or office supply stores) may also be used. Follow manufacturer instructions for use. Test the Smoke/CO Alarm. Never use
water, cleaners or solvents since they may damage the unit.
• If the Smoke/CO Alarm becomes contaminated by excessive dirt, dust and/or grime, and cannot be cleaned to avoid unwanted alarms, replace the unit
immediately.
• Relocate the unit if it sounds frequent unwanted alarms. See “Where This Alarm Should Not Be Installed” for details.
Actual battery service life depends on the Smoke/CO Alarm and the environment in which it is installed. Regardless of the manufacturer’s suggested battery life, you
MUST replace the Alarm immediately once the unit starts “chirping” (the “low battery warning”).
CONFORMS TO
UL STD 217 AND
UL STD 2034
Model PC910
INTRODUCTION
All First Alert® Smoke Alarms conform to regulatory requirements, including UL217 and are designed to detect particles of combustion. Smoke particles
of varying number and size are produced in all fires.
Ionization technology is generally more sensitive than photoelectric technology at detecting small particles, which tend to be produced in greater amounts by
flaming fires, which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a wastebasket, or a
grease fire in the kitchen.
Photoelectric technology is generally more sensitive than ionization technology at detecting large particles, which tend to be produced in greater amounts by
smoldering fires, which may smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each level and in every bedroom of your home.
___________________________________________________________________________________________________________________________
FIRE SAFETY TIPS
Follow safety rules and prevent hazardous situations: 1) Use smoking materials properly. Never smoke in bed. 2) Keep matches or lighters away from children; 3)
Store flammable materials in proper containers; 4) Keep electrical appliances in good condition and don’t overload electrical circuits; 5) Keep stoves, barbecue grills,
fireplaces and chimneys grease- and debris-free; 6) Never leave anything cooking on the stove unattended; 7) Keep portable heaters and open flames, like candles,
away from flammable materials; 8) Don’t let rubbish accumulate. Keep alarms clean, and test them weekly. Replace alarms immediately if they are not working
properly. Smoke Alarms that do not work cannot alert you to a fire. Keep at least one working fire extinguisher on every floor, and an additional one in the kitchen.
Have fire escape ladders or other reliable means of escape from an upper floor in case stairs are blocked.
INSTALLATION
WHERE TO INSTALL THIS ALARM
MINIMUM COVERAGE FOR SMOKE ALARMS, as recommended by the National Fire Protection Association (NFPA), is one Smoke Alarm on every floor, in every
sleeping area, and in every bedroom (See “Regulatory Information For Smoke Alarms” for details on the NFPA recommendations). For CO Alarms, the National
Fire Protection Association (NFPA) recommends that a CO Alarm should be centrally located outside of each separate sleeping area in the immediate vicinity of the
bedrooms. For added protection, install additional CO Alarms in each separate bedroom, and on every level of your home. NOTE: For added protection, install an
additional Smoke/CO Alarm at least 15 feet (4.6 meters) away from the furnace or fuel burning heat source where possible. In smaller homes or in manufactured
homes where this distance cannot be maintained, install the Alarm as far away as possible from the furnace or other fuel burning source. Installing the Alarm closer
than 15 feet (4.6 meters) will not harm the Alarm, but may increase the frequency of unwanted alarms.
In general, install combination Smoke and Carbon Monoxide Alarms:
• On every level of your home, including finished attics and basements.
• Inside every bedroom, especially if people sleep with the door partly or completely closed.
• In the hall near every sleeping area. If your home has multiple sleeping areas, install a unit in each. If a hall is more than 40 feet (12 meters) long, install a unit at
each end.
• At the top of first-to-second floor stairs.
• At the bottom of the basement stairs.
• For additional coverage, install Alarms in all rooms, halls, and storage areas,
where temperatures normally remain between 40˚ F and 100˚ F (4.4˚ C and 37.8˚ C).
IF YOUR SMOKE/CO ALARM SOUNDS
WHAT TO DO FIRST–IDENTIFY THE TYPE OF ALARM
“ALARM-MOVE TO FRESH AIR”
If you hear the CO alarm horn and the CO red light is flashing,
move everyone to a source of fresh air.
DO NOT remove the batteries!
Type of Alarm What You See and Hear
Carbon Monoxide (CO)
CO LED: Flashes Red
Horn: 4 beeps, pause, 4 beeps, pause
Smoke
Smoke LED: Flashes Red
Horn: 3 beeps, pause, 3 beeps, pause
SUGGESTED AREAS FOR INSTALLING
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
SMOKE ALARM WITH
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION
SMOKE/CO ALARMS
SMOKE ALARMS
KEY:
Suggested locations are based on
NFPA recommendations (NFPA 72
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always
refer to national and local codes
before beginning any installation.
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
© 2015 BRK Brands, Inc. All rights reserved. Distributed by BRK Brands, Inc. First Alert® is registered trademark of The First Alert Trust
3901 Liberty Street Road, Aurora, IL 60504-8122 Consumer Affairs: (800) 323-9005 • www.firstalert.com www.brkelectronics.com • 2/15
Printed in Mexico • M08-0407-009
Y
Installed on Replace by
HOW TO INSTALL THIS ALARM
This combination Smoke/CO Alarm was designed to be mounted on the ceiling or wall. It is not a tabletop device. You must install this device on the ceiling or
wall as outlined below. Read “Where To Install This Alarm” before starting.
• Do not connect this unit to any other alarm or auxiliary device. It is a single-station unit that cannot be linked to other devices. Connecting anything
else to this unit may prevent it from working properly.
• Do not install this unit over an electrical junction box. Air currents around junction boxes can prevent smoke from reaching the sensing chamber and
prevent the unit from alarming. Only AC powered units are intended for installation over junction boxes..
TOOLS YOU WILL NEED:
THIS UNIT IS DESIGNED TO BE MOUNTED ON THE CEILING, OR ON THE WALL IF NECESSARY.
• Pencil
• Drill with 3/16” (5 mm) drill bit
• Standard flathead screwdriver
• Hammer
THE PARTS OF THIS
SMOKE/CO ALARM
1 Test/Silence Button
2 Power/Smoke Alarm and
CO Alarm LED
1 Mounting bracket
2 Mounting slots
FOLLOW THESE SIMPLE STEPS
1. Turn alarm upside down so the circular shape is located in the upper left corner of the alarm.
2. If mounting bracket is attached to alarm, lift to separate it from the base.
3. Hold the mounting bracket against the ceiling
(or wall) so the arrow located on the mounting
plate is pointing to the left. (The circular shape
will now be in upper right-hand corner). Trace
around the insides of the mounting slots.
4. Put the unit where it won’t get covered with
dust when you drill the mounting holes.
5. Using a 3/16” (5 mm) drill bit, drill a hole
through the center of the oval outlines you
traced in step #3.
6. Insert the plastic screw anchors (in the plastic
bag with screws) into the holes. Tap the screw anchors gently
with a hammer, if necessary, until they are flush with the ceiling
or wall.
7. Line the mounting bracket up over the plastic screw anchors.
Screw the mounting bracket to the ceiling or wall through the
mounting slots using the two screws provided.
8. Activate the battery. Move the activation switch to “ON”
position against tab stop. Unit will not mount on mounting
bracket unless activated. Once unit is activated, it cannot be
turned off.
NOTE: After you activate the battery, the power indicator light
may flash. (If the unit alarms, the light will blink rapidly, and
the horn will repeatedly sound 3 beeps, pause, 3 beeps.)
9. Attach the Smoke/CO Alarm to the mounting bracket. Hold
alarm as shown in diagram. Place alarm on mounting bracket
and slide to the right until locked into place.
NOTE: Once the Smoke/CO Alarm is snapped onto the
mounting bracket,
you can rotate the Smoke/CO Alarm to adjust the alignment.
10. Test the Smoke/CO Alarm. See “Weekly Testing.”
11. To Permanently Deactivate the Smoke/CO Alarm. After
10 years of operation or Low Battery warning, deactivate the
Alarm: Insert a tool below edge where shown and break tab.
Then slide activation switch to DEACTIVATE mode.
NOTE: At end of life or low battery indication (chirp): unit
must be put in to deactivation mode to deactivate remaining
stored energy in battery. Unit will no longer function once
put into this mode. Unit will resist re-mounting.
NOTE: Be sure to mount the product in the orientation
specified in the next steps as this provides the most
stability for mounting the product to the wall or ceiling.
ON DEACTIVATE