6 FAULT FINDING
The following faults and probable cause/s have been listed with the assumption that
all basic checks have been carried out. Example, product has power, door is closing
correctly etc.
6.1 Compressor Won’t Start
Check continuity of overload. If no continuity replace overload.
Check Start and Run Winding (as per specifications).
Check Run Capacitor.
(Manual Compressor Starting Device can be used to confirm diagnostics.)
6.2 Compressor Starts, Runs And Then Stops
Check connections at the fusite plug, overload and control module connections.
Check supply voltage.
(Manual Compressor Starting Device can be used to confirm diagnostics.)
6.3 Compressor Humming
Check continuity of overload. If no continuity replace overload.
Check connections at the fusite plug, overload and control module connections.
Check Start and Run Winding (as per specifications).
Check Run Capacitor.
6.4 PC Too Cold
Check resistance of variable resistor.
Check resistance of PC sensor as per table.
Check cooling plate for frost pattern. Full frost pattern is required. If not a full
frost pattern, check product for shortage of refrigerant or inefficient compressor.
Check temperatures of cooling plate both intake and exit of plate. If temperature
of intake differs from exit temperature, further investigation is required.
6.5 PC Warm
Check setting of control knob.
Check resistance of variable resistor.
Check resistance of PC sensor as per table.
Check if cooling plate has normal frost pattern. If not, further investigation is
required.
6.6 FC Too Cold
Check setting of control.
Check if PC sensor is in correct position.
Check resistance of PC sensor as per table.
Check if FC Evaporator has normal frost pattern. Checking temperature of the FC
evaporator and cooling plate is recommended to rule out or confirm system or
compressor fault/s.