Installation (cont.)
FGRIO Master
(1) Rx, Tx, B+
Receive, Transmit, and Power are available on screw terminals of the FGRIO
Master terminal block as well as the 10 pin header.
(2) Analog Output
The Analog Output wire is connected from the Analog Output 1,2,3 or 4 screw ter-
minal on the FGRIO Master terminal block to the Analog Input of the RTU
(destination device).
Common Ground is required. It is recommended to run a Ground wire from an
FGRIO Master Ground screw terminal to Ground on the RTU.
NOTE: Analog Output is 1-5 V at low current, so any 4-20 mA current sensing resistor
on the RTU MUST BE REMOVED. If in doubt as to whether RTU-internal resistors
are active, test the link with a full scale input.
(3) Digital Output
The Digital Output wire is connected from the Digital Output 1,2,3 or 4 screw termi-
nal on the FGRIO Master terminal block to the Digital Input of the RTU (destination
device).
Common Ground is required. It is recommended to run a Ground wire from the
FGRIO Master Ground screw terminal to Ground on the RTU.
NOTE: The Digital Output actively drives Low (.4V) and High (4.0V). Remove any
RTU input pull-up resistor, if less than 10 K ohms. Verify that signal levels meet the
RTU input requirements after connection to the RTU.
(4) Digital Input
The RTU Digital Output Wire is connected to Digital Input 1,2,3 or 4 screw terminal
on the terminal block of the FGRIO Master. An internal 10Kohm pullup to +5V is
provided.
The RTU Ground Wire is connected to any of the Ground screw terminals on the
terminal block of the FGRIO Master. Some RTUs use isolated I/O and may require
a ground connection for each input and output.
(5) Sensor Power
To minimize power drain of the IO Slave Solar/Battery System, an input terminal
called Sensor Power is provided on the FGRIO Master terminal block. Sensor
Power has an internal 10 Kohm pull-down to Ground.
If the RTU provides a switched sensor power output, connect it to this terminal.
Verify that the level at Sensor Power falls to < 1.0 V when de-asserted to ensure the
slaves will mirror. If not, connect additional pull-down resistance externally.