Service Manual
RoomAir Conditioners
93011400_06
Fixed chassis, cool only
CCF05A10A, CCF06A10A, CCF08A10A, CCF10A10A
CCF12A10A
Slide out chassis, cool only
CCW06B10A, CCW08B10A, CCW10B10A, CCW12B10A
CCW15B10A, CCW18B30A, CCW24B30A
Slide out chassis, heat & cool
CEW08B11A, CEW12B33A, CEW18B33A, CEW24B33A
Chill Premiere Series Models (R-410A Refrigerant)
Unifit Series Models (R-410A Refrigerant)
Cool Only
UCT08A10A, UCT10A10A, UCT10A30A,
UCT10A30B,UCT12A10A, UCT12A30A, UCT14A30A,
UCT14A30B
Cool with Electric Heat
UET08A11A, UET10A33A, UET12A33A, UET14A33A
Question and Answer IconNeed help?

Do you have a question about the Friedrich CCF06A10A and is the answer not in the manual?

Friedrich CCF06A10A Specifications

General IconGeneral
Cooling Capacity6, 000 BTU
RefrigerantR-32
Voltage115V
TypeWindow
Operating Frequency60 Hz
Noise Level (High)52 dB

Summary

SPECIFICATIONS

OPERATION

OPERATION PRINCIPLES

TROUBLESHOOTING

Product Does Not Operate Troubleshooting Flowchart

A troubleshooting flowchart to diagnose why the product does not operate at all, checking voltage and PCB.

Indoor Fan Operation Troubleshooting Flowchart

A troubleshooting flowchart to diagnose issues when the indoor fan does not operate, checking connectors, motors, and PCB.

Compressor;Outdoor Fan Operation Troubleshooting

A flowchart for troubleshooting when the compressor or outdoor fan does not operate, checking sensors, connectors, and OLP.

Display E1 or E2 Error Code Resolution

Provides steps to resolve display errors E1 or E2, focusing on sensor connections and PCB replacement.

COMPONENT TESTING

Compressor Locked Rotor Voltage and Amperage Tests

Details procedures for testing compressor locked rotor voltage (LRV) and running amperage (RLA).

Compressor Resistance and Efficiency Checks

Covers single-phase resistance tests, ground tests, and methods to check compressor efficiency and diagnose valve failures.

Fan Motor and Capacitor Testing

Explains how to test fan motors and capacitors, including capacitor connections and checks for open or shorted states.

R-410 A SEALED SYSTEM REPAIR

Refrigerant Charging and System Operation Effects

Discusses proper refrigerant charging methods, the importance of correct charge, and the effects of over/undercharging on unit performance.

Diagnosing Undercharged Refrigerant Systems

Explains how to identify and diagnose undercharged refrigerant systems, including listening for sounds and checking pressures.

Diagnosing Overcharged Refrigerant Systems

Details how to identify and diagnose overcharged refrigerant systems, noting symptoms like noisy compressors and high pressures.

Diagnosing Restricted Refrigerant Systems

Covers the identification and diagnosis of partial and complete restrictions within the refrigerant system, including symptoms and checks.

Sealed System Charging Method Procedure

Details the step-by-step process for the Weighed in Charge Method for sealing system charging and repairs.

Compressor Replacement Procedure

Guides on replacing a compressor, including electrical and refrigeration tests, system evacuation, and leak testing.

Compressor Burnout Replacement Procedure

Outlines the special procedure for compressor replacement specifically in cases of compressor burnout, including flushing and system cleaning.