The following alarms are visible in the SERVICE menu, under ALARMS:
Overheat.cond. overheated condenser alarm: the maximum temperature according to parameter C6 has been reached.
Locked Comp. locked compressor alarm: the maximum temperature according to parameter C7 has been reached.
Probe 1 faulty air probe error: check the integrity and temperature of the probe and the instrument-probe connection.
Probe 2 faulty evaporator probe error: check the integrity and temperature of the probe and the instrument-probe connection.
Probe 3 faulty condenser probe error: check the type, integrity and temperature of the probe and the instrument-probe connection.
Rtc Error clock module error: it is necessary to reset the equipment time and date.