Fuji Electric frenic-hvac - User Manual

Fuji Electric frenic-hvac
746 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
24A7-E-0069d

Table of Contents

Other manuals for Fuji Electric frenic-hvac

Questions and Answers

  • Y
    ydanielsSep 9, 2025
    How to fix a Fuji Electric Controller output phase loss?
    • F
      frederick83Sep 9, 2025
      To correct an output phase loss in your Fuji Electric Controller: * Measure the output current and replace the output wires if necessary. * Measure the output current and consider replacing the motor if needed. * Check if any screws on the inverter output terminals have become loose and tighten them to the recommended torque. * Ensure that you are not using single-phase motors, as they are not compatible.
  • A
    amorrisAug 25, 2025
    How to reset Fuji Electric Controller password protection (inverter lock)?
    • F
      Frank BassAug 25, 2025
      To reset the password protection (inverter lock) on your Fuji Electric Controller, you can: * Delete the password setting. Delete the password with the all clear command (PRG >5 > 2 >10). Note that when doing so, all inverter settings will also be initialized simultaneously. Then, reset the password. * To clear the Lok alarm while retaining the inverter settings, notify Fuji Electric and append the clear application number (PRG > 5 > 8). Fuji Electric will ensure that no illegal operations have been performed, and then issue an alarm clear code.
  • P
    Patricia PriceAug 25, 2025
    What does it mean when my Fuji Electric Inverter displays an overvoltage error?
    • S
      sherry76Aug 26, 2025
      This means the DC link bus voltage has exceeded the overvoltage detection level.
  • C
    Cristian KellerSep 23, 2025
    How to reset Mock alarm on Fuji Electric Controller?
    • K
      Kelly LambertSep 23, 2025
      To escape from the mock alarm state on your Fuji Electric Controller, press the key to reset.
  • X
    xhermanSep 9, 2025
    How do I troubleshoot a Fuji Electric Controller external alarm?
    • K
      Kimberly RivasSep 10, 2025
      To troubleshoot an external alarm on your Fuji Electric Controller: * Check the operation of external equipment and remove the cause of the alarm that occurred. * Ensure that the external alarm signal wiring is correctly connected to the terminal to which the "Enable external alarm trip" terminal command THR has been assigned (Any of E01 through E07, E98, and E99 should be set to "9."). Connect the external alarm signal wire correctly. * Verify that the "Enable external alarm trip" terminal command THR has not been assigned to an unavailable terminal (with E01 through E07, E98, or E99). Correct the assignment if necessary.
  • S
    stephenrodgersSep 17, 2025
    How to resolve Enable circuit error on Fuji Electric Controller?
    • H
      harriskevinSep 17, 2025
      To resolve an enable circuit error on your Fuji Electric Controller: * Check whether the interface board is securely attached to the unit. The alarm will be cleared by turning ON the power again. * Check whether outputs from safety switches and so on are input to both terminals EN1 and EN2 with the same logic (High/High or Low/Low). The alarm will be cleared by turning ON the power again. * If unable to clear the error with the above procedures, the inverter condition is abnormal.
  • A
    Alexandra ConwaySep 3, 2025
    What does it mean when my Fuji Electric Inverter displays PID feedback error?
    • J
      jacob43Sep 3, 2025
      This means the PID feedback signal wire is broken under PID control.
  • N
    Nathan ChristianSep 3, 2025
    What does it mean when my Fuji Electric Inverter displays external alarm?
    • C
      cordovaloriSep 4, 2025
      This means that the external alarm THR was entered.
  • A
    amy72Sep 23, 2025
    What to do if Fuji Electric Controller shows Low battery?
    • D
      danielhubbardSep 23, 2025
      To address a low battery issue on your Fuji Electric Controller: * Check whether the battery is securely attached to the connector on the unit board. If normal battery voltage is detected, the cause of the problem will be cleared, and resetting will be possible. * Check whether the battery is degraded and replace the battery with a new one if necessary.
  • R
    Ryan KingAug 29, 2025
    What does it mean if my Fuji Electric Inverter displays a RS-485 communications error (COM port 1)?
    • R
      Ryan WaltersAug 29, 2025
      A communications error has occurred during RS-485 communication.

Fuji Electric frenic-hvac Specifications