ADDITIONAL CHARGE OF REFRIGERANT
Refrigerant suitable for a piping length of 7.5m is charged in the outdoor
unit at the factory.
When the piping is longer than 7.5m, additional charging is necessary.
For the additional amount, see the table below.
ASY9RSJCW /AOY9RSJC
Between 7.5m and 10m, when using a connection pipe other than that in
the table, charge additional refrigerant with 16g/1m as the criteria.
(The maximum length of the piping is 10m. If the units
are further apart than this, correct operation can not
be guaranteed.)
Between 7.5m and 15m, when using a connection pipe other than that in
the table, charge additional refrigerant with 16g/1m as the criteria.
(The maximum length of the piping is 15m. If the units
are further apart than this, correct operation can not
be guaranteed.)
Pipe
length
7.5m 10m
40gNone
Additional
refrigerant
ASY12RSJCW / AOY12RSJC
Pipe
length
7.5m 10m
40g
15m
120gNone
Additional
refrigerant
2
2003.06.17