7. Additional charge calculation
7-1. Models: ROG07KPCA and ROG09KPCA
Refrigerant type R32
Refrigerant amount g 550
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100
7-2. Model: ROG12KPCA
Refrigerant type R32
Refrigerant amount g 590
¢ Refrigerant charge
Total pipe length m 15 or less 20 (Max.)
20 g/m
Additional charge g 0 100