INDOOR UNIT
H x W x D
(mm)
H x W x D
(mm)
240 x 1,660 x 700
OUTDOOR UNIT 1,165 x 900 x 330
DIMENSIONS
INDOOR UNIT GROSS / NET (kg)
GROSS / NET (kg)
62 / 49 61 / 48
OUTDOOR UNIT
116 / 109 120 / 113
WEIGHT
SPECIFICATIONS
TYPE COOLING COOLING & HEATING
INDOOR UNIT
ABY45FBAG ABY45UBAG
OUTDOOR UNIT
AOY45FMAXT AOY45UMAXT
COOLING CAPACITY (kW)
12.7 12.7
HEATING CAPACITY (kW) ---- 14.3
POWER SOURCE
(V) 400
3 / 50
RUNNING CURRENT
COOLING 7.7 7.7
(A)
HEATING ---- 7.7
INPUT WATTS
(kW)
(kW/kW)
COOLING 4.38 4.38
HEATING ---- 4.39
E.E.R.
COOLING 2.90 2.90
HEATING ---- 3.26
STARTING CURRENT
(A) 67 67
MOISTURE REMOVAL
5.0 5.0
FAN MOTOR
TYPE
Hermetic type, 2 poles, 3-phase, Induction moto, Scroll
DISCRIMINATION BN52YEAMT
REFRIGERANT R410A
3,400 g
HIGH
FAN SPEED
INDOOR MED
(r.p.m.)
LOW
OUTDOOR
INDOOR
(m /h)
3
AIR FLOW
OUTDOOR
1,100
1,000
850
780
1,850
6,100
ELECTRICAL DATA
COMPRESSOR
( /hr)
( /Hz)
MAX PIPE LENGTH
50 m
MAX PIPE HEIGHT
30 m
REMOTE CONTROLLER TYPE
WIRELESS
ADDITIONAL REFRIGERANT CHARGE (R410A)
PIPE LENGTH
FULL CHARGE
AMOUNT
20 m
( 66 ft )
30 m
( 99 ft )
40 m
( 132 ft )
50 m
( 164 ft )
ADDITIONAL CHARGE
3,400 g (119.9 oz)
3,800 g (134.0 oz)
4,200 g (148.2 oz)
4,600 g (162.3 oz)
40 g / m (1.41oz / 3.3 ft)