10) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number Setting value Setting description Factory setting
60
00 Operation status
01—08 (Setting prohibited)
09 Error status
10 Indoor unit fan operation status
11 (Setting prohibited)
12 Setpoint attainment status
11) Special cooling operation
Stabilizes the cooling operation when the outdoor temperature is low.
Operation mode: Fixed at COOL
Airflow: Fixed at HIGH
Set temperature: 24°C to 30°C
Function number Setting value Setting description Factory setting
96
00 Disable
01 Enable
NOTES:
Connect the optional wired remote controller to change the setting value to “Enable” (01).
Do not use the wireless remote controller after changing the setting value to “Enable” (01).
If the wired remote controller becomes noncommunicable after setting “Enable” (01), the cooling
operation starts automatically.
If dew condenses on the indoor unit surface after setting “Enable” (01), set the setting value
back to “Disable” (00).