1-4. Rotation number of compressor at normal start-up
Rotation number of compressor soon after starting is controlled as below.
Rotation number I
Rotation number II
Rotation number III
Rotation number IV
Rotation number V
Rotation number VI
Rotation number VII
Time 1
Time 2 Time 3
Time 4
Time 5
Time 6
Time 7
Rotation number VIII
Time 8
Normal operation
Rotation
number
(rps)
I II III IV V VI VII VIII
25 42 53 61 65 75 85 92
Time (sec)
1 2 3 4 5 6 7 8
90 150 270 330 390 450 570 630
Special operation
Rotation
number
(rps)
I II III IV V VI VII VIII
25 42 53 61 65 75 85 92
Time (sec)
1 2 3 4 5 6 7 8
225 305 605 665 725 785 855 1,000
NOTES:
Normal operation:
Cooling and dry mode
Below 3 hours from the compressor stop and the compressor thermistor ≥ 15°C
After defrost operation
Other than when the compressor starts for the first time since the breaker turns on
Special operation:
Other than the normal operation condition
When the compressor starts for the first time since the breaker turns on