En-4
SPECIFICATIONS
MODEL
ARXA24
GBLH
ARXA30
GBLH
ARXA36
GBLH
ARXA45
GBLH
POWER SOURCE 230 V ~ 50/60 Hz
AVAILABLE VOLT-
AGE RANGE
198 to 264 V (50Hz) , 198 to 253 V (60Hz)
COOLING
CAPACITY
[kW] 7.1 9.0 11.2 12.5
[BTU/h] 24,200 30,700 38,200 42,700
HEATING
CAPACITY
[kW] 8.0 10.0 12.5 14.0
[BTU/h] 27,300 34,100 42,700 47,800
INPUT
POWER
[W] 94 108 194 240
CURRENT [A] 0.60 0.69 1.18 1.43
SOUND PRESSURE LEVEL
HIGH dB [A] 31 34 37 41
MED dB [A] 27 32 35 38
LOW dB [A] 23 29 33 36
DIMENSIONS & WEIGHT
HEIGHT [mm] 270
WIDTH [mm] 1,135
DEPTH [mm] 700
WEIGHT [kg] 36 40
Acoustic Noise Information :
The maximum sound pressure level is less than 70 dB (A) for both
indoor unit and outdoor unit. According to IEC 704-1 and ISO 3744.
Standard static pressure :
ARXA24: 40 Pa, ARXA30/36: 50 Pa, ARXA45: 60 Pa