2-16. NETWORK CONVERTOR
2-16-1. MODEL: UTY-VTGX
SWITCH POSITION
Set network convertor rotary switch SET1, and Dip switch SET2, SET3.
REFRIGERANT CIRCUIT ADDRESS SETTING (SET 1)
z
Example
Refrigerant
circuit
address
SW setting
SET1 (x10)
(10 digit)
SET1 (x1)
(1 digit)
01
0 1
99
9 9
*Setting range 00 - 99 (Arbitrary numbers can be set)
*When connecting the Network convertor for Single split AC , set up the number so that the Refrigerant circuit ad-
dress number of outdoor unit and indoor unit does not overlap .
And the sum total of the Refrigerant circuit address of Network convertor for Single split AC and the Refrigerant
circuit address of the outdoor unit and the indoor unit is a maximum of 100.
TERMINAL RESISTER SETTING (SET 2)
Set to "ON" when there is no termination resistance in the segment separated by the signal amplier.
(Default: OFF)
REMOTE CONTROLLER 2WIRE/3WIRE SWITCHING (SET 3)
Match with the setting of the used indoor unit.
Set matched with the connection method of the remote controller cable to be connected.
(Default: 2WIRE)
- (07 - 133) -