2-16-2. MODEL: UTY-VGGXZ1
SWITCH POSITION
Set network convertor rotary switch SW110 and SW111.
SW110 SW111
Network convertor PCB
REFRIGERANT CIRCUIT ADDRESS SETTING
For Split system
z
Example
Refrigerant
circuit
address
SW setting
Rotary SW110
(10 digit)
Rot ar y SW111
(1 digit)
01
0 1
99
9 9
*Setting range 00 - 99 (Arbitrary numbers can be set)
*When connecting the Network convertor for Single split AC , set up the number so that the Refrigerant circuit ad-
dress number of outdoor unit and indoor unit does not overlap .
And the sum total of the Refrigerant circuit address of Network convertor for Single split AC and the Refrigerant
circuit address of VRF outdoor units and the indoor unit is a maximum of 100.
- (07 - 134) -