1-3. MANUAL ADDRESS SETTING METHOD
ADDRESS SETTING DESCRIPTION
z
Refrigerant circuit address (Set A, Set D and Set O)
In case of 2 or more refrigerant system in VRF network system, each refrigerant system should
be set an exclusive refrigerant circuit address.
Refrigerant system : It means same refrigerant circuit which has connected between outdoor
unit and indoor unit by piping.
00 01 02 00 01 0201 01 010 1 0 02 02 020 1 2 00 01 0225 25 250 1 2
0001 0101
2 3
001 025201101
3 3 1 2 2
125
02
Refrigerant system 1 Refrigerant system 2 Refrigerant system 25
z
Example
Outdoor unit (Set A), Indoor unit (Set D),
RB unit (Set O)
Refrigerant
circuit
address
Rotary SW setting
REF AD x10 REF AD x1
01
0 1
11
1 1
25
2
5
50
5 0
Setting range 00 - 99(Arbitrary numbers can be set)
All the indoor unit, all the RB unit and outdoor unit in same refrigerant circuit should be set
same address.
- (07 - 07) -
FUNCTION
SETTING
FUNCTION
SETTING