En-5
Wall height condition Necessary installation space
When H3 is 59 in (1500 mm) or less L3 20 in (500 mm)
When H3 is 59 in (1500 mm) or more L3 20 in (500 mm) + h3 ÷ 2
When H4 is 19 in (500 mm) or less L4 8 in (200 mm)
When H4 is 19 in (500 mm) or more L4 8 in (200 mm) + h4 ÷ 2
When H5 is 19 in (500 mm) or less L5 8 in (200 mm)
When H5 is 19 in (500 mm) or more L5 8 in (200 mm) + h5 ÷ 2
Fig. 4
h3
L3
L4
h4
H3
H4
<Side view>
<Front>
<Rear>
Wall
Wall
59 in
(1500 mm)
19 in
(500 mm)
Fig. 5
L5
L5
h5
h5
H5
H5
<Front view>
Wall
19 in
(500 mm)
19 in
(500 mm)
Wall
Fig. 6
<Top view>
32 in
(800 mm)
or more
32 in
(800 mm)
or more
1 in
(20 mm)
or more
1 in
(20 mm)
or more
L4
L3
L5L5
Fig. 7
<Top view>
20 in
(500 mm)
or more
40 in
(1000 mm)
or more
1 in
(20 mm)
or more
1 in
(20 mm)
or more
L4
L3
L5
L5
3. 3. 2. When install near unlimited height wall
(1) Single and multiple installations
There are no restrictions on the height of the wall.
The wall (without height restrictions) must not exist on the both sides (left / right)
of outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor
unit.
• Provide installation spaces other than L6 in accordance with the conditions
shown in the gure below.
Ventilation resistance can be ignorable when the distance from a wall or product,
etc. is larger than 79 in (2 m).
When installing with the rear of the outdoor unit facing the wall side
Condition Necessary installation space
When B 16 in (400 mm) L6 8 in (200 mm)
When 1 in B < 16 in
(When 20 mm B < 400 mm)
L6 8 in + (16 in - B) × 3
(L6 200 mm + (400 mm - B) × 3)
Fig. 8 Single installation
<Top view>
<Front>
<Rear>
8 in
(200 mm)
or more
4 in
(100 mm)
or more
Fig. 9 Multiple installations
<Top view>
<Front>
<Rear>
8 in
(200 mm)
or more
B
L6
B
8 in
(200 mm)
or more
8 in
(200 mm)
8 in
(200 mm)
32 in
(800 mm)
or more
Example :
When B is made 8 in (200 mm)
L6 8 + (16 - 8) × 3 = 32 in
(L6 200 + (400-200) × 3 = 800 mm)
When installing with the FRONT of the outdoor unit facing the wall side
Fig. 10
<Top view>
20 in
(500 mm)
or more
8 in (200 mm) or more
Wall
Wall
Fig. 11
Fig.
<Top view>
20 in
(500 mm)
or more
8 in
(200 mm)
or more
1 in
(20 mm)
or more
1 in
(20 mm)
or more
Wall
Wall
(2) Multiple condensers Installation
The wall (without height restrictions) must not exist on the both sides (left / right) of
outdoor unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
Ventilation resistance can be ignorable when the distance from a wall or product,
etc. is larger than 79 in (2 m).