EasyManuals Logo

Fujitsu AO G12KATA Series Service Manual

Fujitsu AO G12KATA Series
471 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #248 background imageLoading...
Page #248 background image
2-16. E: 45. Refrigerant leakage sensor error (Indoor unit)
Indicator Indoor unit
Operation indicator 4 time flash
Timer indicator 5 time flash
Economy indicator Continuous flash
Error code E: 45
Detective actuator Refrigerant leakage sensor
When refrigerant leakage sensor open, short circuit, or
abnormal voltage of drive circuits detected.
Forecast of cause
Connector connection failure
Harness disconnection
Refrigerant leakage sensor deterioration
System is down.
Check point 1. Check connection of connector
• Check if connector is loose or removed.
• Check erroneous connection.
• Check if refregerant leakage sensor cable is open.
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Replace refrigerant leakage sensor
• If an abnormality (failure) occurs, the refrigerant leakage sensor needs to be replaced.
↓
End
2-16. E: 45. Refrigerant leakage sensor error (Indoor unit) - (03-32) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AO G12KATA Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AO G12KATA Series and is the answer not in the manual?

Fujitsu AO G12KATA Series Specifications

General IconGeneral
BrandFujitsu
ModelAO G12KATA Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals