7-3. Current release control
The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur-
rent limit value set according to the outdoor temperature.
The compressor frequency returns according to the operation mode, when the current becomes low-
er than the release value.
¢ Model: AOYG12KBTB
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
50°C ≤ Ta 3.5 A 3.0 A
46°C ≤ Ta < 50°C 4.5 A 4.0 A
40°C ≤ Ta < 46°C 6.0 A 5.5 A
12°C ≤ Ta < 40°C 7.0 A 6.5 A
2°C ≤ Ta < 12°C 7.0 A 6.5 A
Ta < 2°C 7.0 A 6.5 A
Heating
17°C ≤ Ta 7.0 A 6.5 A
12°C ≤ Ta < 17°C 8.5 A 8.0 A
5°C ≤ Ta < 12°C 8.5 A 8.0 A
Ta < 5°C 8.5 A 8.0 A
¢ Model: AOYG14KBTB
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
50°C ≤ Ta 3.5 A 3.0 A
46°C ≤ Ta < 50°C 4.5 A 4.0 A
40°C ≤ Ta < 46°C 6.0 A 5.5 A
12°C ≤ Ta < 40°C 8.5 A 8.0 A
2°C ≤ Ta < 12°C 8.5 A 8.0 A
Ta < 2°C 8.5 A 8.0 A
Heating
17°C ≤ Ta 7.0 A 6.5 A
12°C ≤ Ta < 17°C 9.0 A 8.5 A
5°C ≤ Ta < 12°C 9.0 A 8.5 A
Ta < 5°C 9.0 A 8.5 A
¢ Model: AOYG18KBTB
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
50°C ≤ Ta 4.5 A 4.0 A
46°C ≤ Ta < 50°C 4.5 A 4.0 A
40°C ≤ Ta < 46°C 6.0 A 5.5 A
12°C ≤ Ta < 40°C 10.0A 9.5 A
2°C ≤ Ta < 12°C 10.0 A 9.5 A
Ta < 2°C 10.0 A 9.5 A
Heating
17°C ≤ Ta 7.0 A 6.5 A
12°C ≤ Ta < 17°C 9.0 A 8.5 A
5°C ≤ Ta < 12°C 10.5 A 10.0 A
Ta < 5°C 10.5 A 10.0 A