7-5. Compressor temperature protection
When the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. When the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition 108°C
Release condition
80°C
(3 minutes after compressor stop)
7-6. High pressure protection
Trigger condition
Pressure switch: Off (Open: Higher than 4.2 MPa)
Compressor stop
Release condition
Pressure switch: On (Close: Lower than 3.2 MPa)
(3 minutes after compressor stop)
Compressor restart
7-7. Low outdoor temperature protection
When the outdoor temperature sensor detects lower than the trigger condition below, the compres-
sor is stopped.
Operation mode Cooling/Dry Heating
Trigger condition -20°C
Release condition -15°C
7-8. High temperature and high pressure release control
The compressor is controlled as follows.
¢ Models: AOEG30KATA, AOEG36KATA, and AOEG45KATA
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB: 63°C
BC: 55°C
CD: 53°C
DE: 50°C
Zone Operation
Zone A Compressor is stopped.
Zone B
The compressor frequency is decreased.
-15 rps/120 sec.
Zone C -2 rps/120 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E