4-8. Reactor assy
¢ Outdoor unit
Models: AOYG36KQTA, AOYG45KQTA, and AOYG54KQTA
Check point 1. Appearance check
No fissures, breaks, damage, etc. at the body and winding section, terminals section?
Check point 2. Electric check
1 Set the tester to the "Resistance" mode, and check for open/short between both ends of the re-
actor wire (or connector).
2 Judge the result of 1 as follows:
Short Normal
Open Abnormal (open)
*Reference value of DC resistance of reactor 0.132Ω Max (at 25°C)