Trouble shooting 3
INDOOR UNIT Error Method:
Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check Point 1 : Check the connection of terminal
OKOK
Indicate or Display:
Wired Remote Controller
Communication Error
Indoor unit Controller PCB
Wired Remote Controller (Option)
1. Connection failure 2. Wired Remote Controller failure 3. Controller PCB failure
Check & correct the followings.
Check the connection of terminal between Wired Remote Controller and indoor unit,
and check if there is a disconnection of the cable.
When the indoor unit cannot properly receive the signal from
Wired Remote Controller for 1 minute or more.
02-06
Refer to error code table.
>> If it is DC13V, Remote Control is failure. (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is failure. (Check Remote Control once again) >> Replace Controller PCB
Check Voltage at CN14(ARTG30/36LHTA),CN140(ARTG45/54LHTA) of Controller PCB. (terminal 1-3)
(Power supply to Remote Control)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOTG45LATL and is the answer not in the manual?

Fujitsu AOTG45LATL Specifications

General IconGeneral
BrandFujitsu
ModelAOTG45LATL
CategoryAir Conditioner
LanguageEnglish

Related product manuals