Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASU18RLF
[Condition]
Ambient Indoor 59°F, 68°F, 73.4°F, Outdoor 35.6°F, 44.6°F, 53.6°F
(15°C, 20°C, 23°C) (2°C, 7°C, 12°C)
Refrigerant
amount
Standard amount
Piping 7.5m (Height difference 1m)
Power
voltage
60Hz - 230V
Operation
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
Measuring
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
ASU18RLF
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
outdoor unit overall current with the current clamp meter at Power Cable.
length
03-08
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.4
32
(0)
41
(5)
50
(10)
59
(15)
High-pressure of outdoor unit [MPa]
[60Hz-230V]
Outdoor ambient temperature
9.0
9.5
10.0
Outdoor total electric current [A]
[°F]
(°C)
ASU18RLF
[60Hz-230V]
Outdoor ambient temperature
32
(0)
41
(5)
50
(10)
59
(15)
[°F]
(°C)
73.4°F(23°C)
68°F(20°C)
59°F(15°C )
Indoor ambient
temperature °F(°C)
73.4°F(23°C)
68°F(20°C)
59°F(15°C )
Indoor ambient
temperature °F(°C)
temperature
8.5
8.0
7.5
7.0