8. External input and output
With using external input and output functions, this product can be operated inter-connectedly
with an external device.
Connector Input Output Remarks
CN14 Control input
See external input/output
settings for details.
CN16 Operation status output
8-1. External input
With using external input function, some functions on this product can be controlled from an exter-
nal device.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor
unit.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 492 ft (150 m).
The wire connection should be separate from the power cable line.
¢
Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
Unit operation Initial setting after power is on
Starting mode other than initial
setting
Operation mode Auto changeover Mode at previous operation
Set temperature 76 °F (24 °C) Temperature at previous operation
Airflow mode AUTO Mode at previous operation
Air direction (swing) Standard air direction (swing OFF) Air direction at previous operation