Auxiliary heater control by outdoor temperature 1
This control selects heat pump or external heater according to the outdoor temperature. →hen out-
door temperature is high, the heating is performed by using heat pump only.
Operation Condition
Heater on Heater is on as shown in following diagram of heating temperature.
Heater off
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Heat pump only zone
Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
All control temperatures will shift by adjusting “Thon”.
Outdoor temperature zone boundary A and B: Adjustable individually by function setting number
66 and 67.
External heater output
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Tr-Ts
Off
On
*
Tr-Ts ≥ 0.9°F
(0.5°C)
Tr-Ts (=Thon) < -0.9°F (-0.5°C)
*: →hen room temperature stays in this zone for a specific time, auxiliary heater is turned on. For
details, refer to function number 71.
Outdoor temperature zone
Heat pump only zone
(Heat pump)
Combination zone
(Heat pump + Heater)
Heat pump prohibition zone
(Heater)
B: 42.8°F (6°C)*
A: -4°F (-20°C)*
B + 3.6°F (2°C): 46.4°F (8°C)
A + 3.6°F ( 2°C): -0.4°F (-18°C)
Outdoor temp.
*: Adjustable by function setting 66 and 67
3-5. Details of control output function - (05-31) - 3. External input and output (for indoor unit)