Fujitsu AOUH36LPAS1 - Indoor Unit Room Temperature Sensor Correction

Fujitsu AOUH36LPAS1
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2) Room temperature control for indoor unit sensor
NOTE: Before performing this setting, refer to Function 95.
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 78°F and the setting value is “03” (-2°F),
the corrected temp. will be 80°F (78°F - [-2°F]).
The temperature correction values show the difference from the Standard setting “00” (manufactur-
er’s recommended value).
*When Function 95-01 (High insulation) is set, the Standard setting “00” will be the same as “No cor-
rection 0.0 °F (0.0 °C)” (01).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting*
01 No correction 0.0 °F (0.0 °C)
02 -1 °F (-0.5 °C)
More cooling
Less heating
03 -2 °F (-1.0 °C)
04 -3 °F (-1.5 °C)
05 -4 °F (-2.0 °C)
06 -5 °F (-2.5 °C)
07 -6 °F (-3.0 °C)
08 -7 °F (-3.5 °C)
09 -8 °F (-4.0 °C)
10 +1 °F (+0.5 °C)
Less cooling
More heating
11 +2 °F (+1.0 °C)
12 +3 °F (+1.5 °C)
13 +4 °F (+2.0 °C)
14 +5 °F (+2.5 °C)
15 +6 °F (+3.0 °C)
16 +7 °F (+3.5 °C)
17 +8 °F (+4.0 °C)
- 50 -
11-1. Function settings by using remote controller
11. Function settings