11. Safety devices
Type of
protection
Protection form
Model
AOUH30LPAS1 AOUH36LPAS1
Circuit
protection
Current fuse (Main PCB)
250 V, 30 A
250 V, 3.15 A
250 V, 10 A × 2
Fan motor
protection
Thermal protection
Activate
251.6 ±16.2°F (122 ±9°C)
Fan motor stop
Reset
240.8
+18.0
-16.2
°F (116
+10
-9
°C)
Fan motor restart
Compressor
protection
Thermal protection program
(Compressor temp.)
Activate
226.4°F (108°C)
Compressor stop
Reset
After 3 minutes, and 176°F (80°C) or less
Compressor restart
Thermal protection program
(Discharge temp.)
Activate
230°F (110°C)
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection program
(Outdoor temp.)
(Only in COOL and DRY mode)
Activate
5°F (-15°C)
Compressor stop
Reset
14°F (-10°C)
Compressor restart
- 76 -
11. Safety devices
OUTDOOR UNIT
AOUH30-36LPAS1
OUTDOOR UNIT
AOUH30-36LPAS1