EasyManua.ls Logo

Fujitsu AOYG30KBTB - E: 22. Indoor Unit Capacity Error (Indoor Unit)

Fujitsu AOYG30KBTB
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-5. E: 22. Indoor unit capacity error (Indoor unit)
Detective actuator Indoor unit main PCB
When the total capacity of the indoor units does not
match outdoor unit capacity while 3 minutes after power
on.
Forecast of cause
Indoor unit selection is incorrect.
Main PCB failure
Check point 1. Check the total capacity of indoor units
Check the total capacity of the indoor units.
→ If abnormal condition is found, correct it referring to the installation manual or DESIGN & TECH-
NICAL MANUAL.
Check point 2. Replace main PCB
If check point 1 does not improve the symptom, change main PCB.
End
2-5. E: 22. Indoor unit capacity error (Indoor unit) - (03-9) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AOYG30KBTB

Related product manuals