5. INDOOR FAN CONTROL
(1).Fan speed
( Table 5 : Indoor Fan Speed )
AWYZ14LBC
Operat ion mode Air flow mode Speed (rpm)
Hi 1,650
Me+ 1,470
Me 1,350
Lo 1,150
Quiet 1,000
S-Quiet
S-Quiet
820
Cool air
prevention
850
Heating
S-Lo 480
Hi 1,450
Me 1,320
Lo 1,050
Cooling
Fan
Quiet 880
730
850
S-Quiet
Except S-Quiet Except S-Quiet
Dry
730
(2).FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor
fan only runs.
When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
AWYZ18LBC
Operation mode Air flow mode Speed (rpm)
Hi 1,650
Me+ 1,470
Me 1,350
Lo 1,150
Quiet 1,000
S-Quiet
S-Quiet
S-Quiet
820
Cool air
prevention
850
Heating
S-Lo 480
Hi 1,450
Me 1,320
Lo 1,050
Cooling
Fan
Quiet 880
730
850
Dry
730