Check Point 5 : Check Opening and Closing Operation of Valve
Pipe (In)
Pipe (Out)
Hi TEMP.
Pipe (In)
Hi TEMP.
Normal TEMP.
CLOSE
Example : Hot Gas
OPEN
Example : Hot Gas
Pipe (Out)
Hi TEMP.
Pipe (In) Pipe (Out)
Pipe (In) Pipe (Out)
Check Point 6 : Check Strainer
When Valve is closed,
it has a temp. difference between Inlet and Outlet.
If it is open,
it has no temp. difference between Inlet and Outlet.
Strainer normally does not have temperature difference between inlet and outlet as shown in ,
but if there is a difference as shown in , there is a possibility of inside clogged. In this case, replace Strainer.
02-42
Check Point 2 : Check Coil of EEV
Yellow - Brown
Blue - Brown
White - Red
Read wire
46
Resistance value
Check Point 3 : Check Voltage from Main PCB.
DC
at 68°F(20°C)
Remove connector, check each winding
resistance of Coil.
If Resistance value is abnormal, replace EEV.
Remove Connector and check Voltage (DC12V)
Turn on Power and check operation noise.
If an abnormal noise does not show, replace Main PCB.
If it does not appear, replace Main PCB.
Check Point 4 : Check Noise at start up
4
Orange - Red

Other manuals for Fujitsu ARU18RLF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARU18RLF and is the answer not in the manual?

Fujitsu ARU18RLF Specifications

General IconGeneral
BrandFujitsu
ModelARU18RLF
CategoryAir Conditioner
LanguageEnglish

Related product manuals