What to do if my Fujitsu ARU24RLF Air Conditioner remote is not working due to a communication error?
F
fhickmanAug 13, 2025
If you're experiencing a Wired Remote Controller Communication Error with your Fujitsu Air Conditioner, check the voltage. If it's DC12V, the remote control has failed and should be replaced. If it's DC 0V, the Controller PCB has failed and should be replaced after rechecking the remote control.
W
wmartinAug 16, 2025
What to do if my Fujitsu ARU24RLF Air Conditioner has a drainage error?
D
Dylan LindseyAug 17, 2025
If your Fujitsu Air Conditioner is experiencing drainage issues, start by inspecting the float switch for proper operation using a meter to check its on/off switching. If the float switch is defective, replace it. Also, examine the drain hose for any clogs and clear them if necessary. If these steps don't resolve the issue, consider replacing the controller PCB.
C
Curtis TerryAug 20, 2025
How to fix a Fujitsu ARU24RLF Air Conditioner indoor unit fan motor error?
M
Margaret LeachAug 20, 2025
If you're encountering an indoor unit fan motor error with your Fujitsu Air Conditioner, check first the fan and bearing. If either is damaged, replace them. If the motor itself is faulty, replace the indoor unit fan motor. If these steps do not resolve the issue, replace the controller PCB.
J
Jessica LewisAug 25, 2025
What to do if my Fujitsu ARU24RLF shows an indoor room thermistor error?
V
Vickie SimmonsAug 25, 2025
If your Fujitsu Air Conditioner displays an indoor room thermistor error, begin by checking the connector to ensure it is securely attached and properly connected, and verify that the thermistor cable is not open. If the thermistor is either open or shorted, replace it and then reset the power.
A
Andrew JohnsonAug 27, 2025
How to troubleshoot an Indoor Unit Model Information Error on my Fujitsu Air Conditioner?
C
Christina HortonAug 28, 2025
If your Fujitsu Air Conditioner is showing an Indoor Unit Model Information Error, check for external causes such as noise and ensure the ground connection is properly connected. Also, inspect all connectors for looseness or incorrect wiring, and check the PCB for any shorts or corrosion. If the problem persists, consider replacing the Controller PCB.
M
Michael BoydAug 31, 2025
What does an Indoor Unit Capacity Error mean on my Fujitsu ARU24RLF Air Conditioner?
M
Misty McculloughSep 1, 2025
If your Fujitsu Air Conditioner is showing an Indoor Unit Capacity Error, first verify the total capacity of the connected indoor units. If an abnormal condition is found, correct it by referring to the Installation Manual or Design & Technical Manual. If the problem persists, replace the Main PCB of the Outdoor unit.
A
Angel GilbertSep 4, 2025
How to fix a Serial Communication Error (Serial Reverse Transfer Error) on a Fujitsu ARU24RLF Air Conditioner?
M
Michael WatkinsSep 4, 2025
If your Fujitsu Air Conditioner displays a Serial Communication Error (Serial Reverse Transfer Error), check all connection lines between the indoor and outdoor units for any looseness or disconnections, referring to the Installation Manual or Data & Technical Manual for correction. Also, check the voltage of the power supply, ensuring it appears at the outdoor unit terminal L1 - L2 within the range of AC187V - 253V. Check that the indicated value swings between AC90V and AC270V at outdoor unit terminal 1 - 3. If the outdoor fan motor, active filter module, or IPM is abnormal, replace the corresponding part. If all parts are normal, replace the Main PCB.
T
Tracy SmithSep 8, 2025
How to resolve a Damper (Open/Close) simultaneous detection Limit switch error on a Fujitsu Air Conditioner?
U
uraySep 8, 2025
If your Fujitsu Air Conditioner displays a Damper(Open/Close) simultaneous detection Limit switch error, replace the limit switch if it is defective. If the problem persists, replace the Controller PCB.