Model: AOHG36KBTA5
Fan speed is defined by outdoor temperature and compressor frequency.
Unit: rpm
Fan step Cooling or dry Heating
S-HIGH 1,200
13 1,150
12 1,150
11 1,150
10 1,080 1,200
9 920 1,150
8 860 1,080
7 770 990
6 680 860
5 630 800
4 560 700
3 490 640
2 390 600
1 270 570
When the compressor frequency increases, the outdoor fan speed also changes to the higher
speed.
When the compressor frequency decreases, the outdoor fan speed also changes to the lower
speed.
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,200 rpm
3-2. Outdoor fan control - (04-54) - 3. Fan control