EasyManuals Logo

Fujitsu ARXG36KMLA Service Instruction

Fujitsu ARXG36KMLA
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
02-09
Trouble shooting 8
INDOOR UNIT Error Method:
Connection unit number error (Indoor
unit in Wired remote controller system)
Detective Actuators:
Wired remote controller ( 2-Wire )
Indoor unit Controller PCB circuit
Detective details:
When the number of connecting indoor units are out of specified rule.
Forecast of Cause :
1. Wrong wiring / Number of I.U, RC in RCgroup 2. Indoor unit controller PCB defective
Check Point 1 : Wire installation
Wrong number of connecting indoor unit
Check Point 2 : Check Indoor unit controller PCB
Check if controller PCB damage
Check if controller PCB and check the Error after setting remote controller address
Indicate or Display:
Error code : 29
OK
Outdoor unit :
n
: n times blinking
: Light ON: Light OFF
Mode Error L1 L2 L6L5L4L3
2 5
15

Other manuals for Fujitsu ARXG36KMLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ARXG36KMLA and is the answer not in the manual?

Fujitsu ARXG36KMLA Specifications

General IconGeneral
BrandFujitsu
ModelARXG36KMLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals