7) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "→ired re-
mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
→hen the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function number Setting value Setting description Factory setting
48
00 Both ♦
01 →ired remote controller
8) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number Setting value Setting description Factory setting
49
00 Disable
01 Enable
02 Remote controller ♦
00: →hen the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: →hen the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTE: Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter. To confirm if the remote con-
troller has this setting, refer to the operating manual of each remote controller.
9) Primary and secondary settings
Set the indoor unit that is connected to the outdoor unit using a transmission cable as the primary.
Function number Setting value Setting description Factory setting
51
00 Primary ♦
01 Secondary