Detective Actuators: Detective details:
Forecast of Cause:
Check Point 2 : Replace Main PCB
YESYES
NO
Trouble shooting 17
OUTDOOR UNIT Error Method:
Outdoor unit main PCB model
information error
Outdoor unit Main PCB
1. External cause (Noise, temporary open, voltage drop) 2. Main PCB failure
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
Check Point 1-2 : Check external cause
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related
cables near the power line.
Change Main PCB.
Access to EEPROM failed due to some cause after outdoor unit started.
02-18
Indicate or Display:
Error code : 62
Outdoor unit :
n
: n times blinking
: Light ON: Light OFF
Mode Error L1 L2 L6L5L4L3
2 6
2