H x W x DOUTDOOR UNIT
DIMENSIONS
Gross / NetOUTDOOR UNIT
WEIGHT
POWER SOURCE
Cooling
RUNNING
CURRENT
Heating
INPUT WATTS
Cooling
Heating
E.E.R.
Cooling
Heating
Cooling
Heating
STARTING CURRENT
MOISTURE REMOVAL
AIRCIRCULATION
OUTDOOR
FAN MOTOR
Discrimination
High speed
INDOOR
UNIT
Middle speed
Low speed
Upper fan
Lower fan
Discrimination
OUTDOOR
UNIT
(cool / heat)
TYPE
Cooling & Heating
INDOOR UNIT ARYC45LCTU ARYC54LCTU
OUTDOOR UNIT
AOYD45LATT AOYD54LATT
COOLING CAPACITY
HEATING CAPACITY
INDOOR UNIT H x W x D 400 x 1,050 x 500 mm
1,290 x 900 x 330 mm
INDOOR UNIT
Gross / Net
51 kg / 46 kg
117 kg / 107 kg
6.1 A
5.5 A
4.06 kW
3.67 kW
3.08 kW/kW
3.81 kW/kW
6.9 A
6.5 A
4.65 kW
4.37 kW
3.01 kW/kW
3.66 kW/kW
10.0 A
2.5 L/hr
6,900 m3/h
10.0 A
MAXIMUM CURRENT 12.0 A11.0 A
1.5 L/hr
AIRCIRCULATION INDOOR
3,350 m3/h3,350 m3/h
6,900 m3/h
6,200 m3/h
6,900 m3/h
400 V 50 Hz 3 4 W
1,300 r.p.m.
1,150 r.p.m.
1,000 r.p.m.
MFA-60TTFS
1,300 r.p.m.
1,150 r.p.m.
1,000r.p.m.
MFE-54TV
800 / 850 r.p.m.
900 / 850 r.p.m.
800 / 750 r.p.m.
900 / 780 r.p.m.
14.0 kW
16.0 kW
12.5 kW
14.0 kW
ELECTRICAL DATA
TYPE
DISCRIMINATION
WEIGHT (with oil)
REFRIGERANT TYPE R410A
Hermetic type, Inverter,
4 poles, 3 phase,
DC motor, Twin Rotary
808 677 80
25.6 kg
PRECHARGED REFRIGERANT
3,450 g
COMPRESSOR AND REFRIGERANT
2008.11.26 1
SPECIFICATIONS
MAX PIPE LENGTH 75 m
MAX PIPE HEIGHT 30 m
Pipe length
30 m
3,450 g
FULL CHARGE
45 m 4,200 g
60 m 4,950 g
75 m
5,700 g
ADDITIONAL CHARGE
50 g/m
NOISE LEVEL
High speed
47 dB
INDOOR
UNIT
Middle speed 43 dB
Low speed
Cooling
Heating
40 dB
47 dB
43 dB
40 dB
OUTDOOR
UNIT
Note : Static pressure : 100pa
Duct length : Inlet 1m, Outlet 2m
55 dB
56 dB
54 dB
54 dB