Model: AOUH12LPAS1
Fan speed is defined by outdoor temperature and rotation number of compressor.
• Outside air temperature zone selection
Outside air
temperature rises
Z zone
Y zone
F zone
G zone
Outside air
temperature drops
H zone
53.6°F
(
12°C)
35.6°F
(
2°C)
50.0°F
(
10°C)
32.0°F
(
0°C)
17.6°F
(
-8°C)
14.0°F
(
-10°C)
69.8°F
(
21°C)
66.2°F
(
19°C)
Unit: rpm
Fan step
Cooling
Heating
Dry Cooling or dry at low outdoor temp.
Y zone Y zone Z zone F zone G zone H zone
S-HIGH2 — 1,070 — — — — —
S-HIGH1 990 1,070 — — — — —
HIGH 990 1,070 — — — — —
10 — 1,070 — — — — —
9 990 1,070 990 350 260 200 170
8 850 1,070 850 350 260 200 170
7 820 850 820 350 260 200 170
6 820 820 820 250 200 170 170
5 820 700 820 220 200 170 170
4 740 610 740 220 200 170 170
3 660 510 660 220 200 170 170
2 610 510 610 220 200 170 170
1 600 510 600 220 200 170 170
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor rotation number.
Fan speed after defrost control: 1,070 rpm
3-2. Outdoor fan control - (04-15) - 3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS