5. Thermistor resistance values
5-1. Indoor unit
¢ Room temperature thermistor
Temperature °F (°C) Resistance (kΩ) Voltage (V)
14.0 (-10.0) 58.25 0.73
23.0 (-5.0) 44.03 0.93
32.0 (0.0) 33.62 1.15
41.0 (5.0) 25.93 1.39
50.0 (10.0) 20.18 1.66
59.0 (15.0) 15.84 1.94
68.0 (20.0) 12.54 2.22
77.0 (25.0) 10.00 2.50
86.0 (30.0) 8.04 2.77
95.0 (35.0) 6.51 3.03
104.0 (40.0) 5.30 3.27
113.0 (45.0) 4.35 3.49
¢ Heat exchanger temperature thermistor
Temperature °F (°C) Resistance (kΩ) Voltage (V)
-22.0 (-30.0) 1,131.91 0.21
-13.0 (-25.0) 804.52 0.29
-4.0 (-20.0) 579.59 0.40
5.0 (-15.0) 422.89 0.53
14.0 (-10.0) 312.27 0.69
23.0 (-5.0) 233.21 0.88
32.0 (0.0) 176.03 1.10
41.0 (5.0) 134.23 1.36
50.0 (10.0) 103.34 1.63
59.0 (15.0) 80.28 1.92
68.0 (20.0) 62.91 2.21
77.0 (25.0) 49.70 2.51
86.0 (30.0) 39.57 2.79
95.0 (35.0) 31.74 3.06
104.0 (40.0) 25.64 3.30
113.0 (45.0) 20.85 3.53
122.0 (50.0) 17.06 3.73
131.0 (55.0) 14.05 3.90
140.0 (60.0) 11.64 4.02
149.0 (65.0) 9.69 4.19
5-1. Indoor unit - (03-55) - 5. Thermistor resistance values
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu ASUH18LPAS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASUH18LPAS and is the answer not in the manual?

Fujitsu ASUH18LPAS Specifications

General IconGeneral
BrandFujitsu
ModelASUH18LPAS
CategoryAir Conditioner
LanguageEnglish

Related product manuals