Limit of maximum speed based on outdoor temperature
A zone
B zone
C zone
D zone
E zone
F zone
Outdoor
temperature drops
Outdoor
temperature rises
93.2°F
(34°C)
96.8°F
(36°C)
86.0°F
(30°C)
66.2°F
(19°C)
50.0°F
(10°C)
32.0°F
(0°C)
89.6°F
(32°C)
69.8°F
(21°C)
53.6°F
(12°C)
35.6°F
(2°C)
Unit: rps
Model name
Outdoor
temperature zone
Indoor unit fan mode
HIGH MED LOW QUIET
ASUH18LPAS
A zone 80 46 36 22
B zone 80 46 36 22
C zone 80 46 36 22
D zone 50 39 32 22
E zone 50 39 32 22
F zone 50 39 32 22
ASUH24LPAS
A zone 111 46 36 26
B zone 111 46 36 26
C zone 111 46 36 26
D zone 54 39 32 26
E zone 54 39 32 26
F zone 54 39 32 26