Trouble Shooting
What the separate wires do in the interconnecting cables
Note – Wires are 240V Live except where marked neutral or Earth or signal.
Cables marked Signal are digital pulses and you should not attempt to measure these with a meter.
Fujitsu Trouble Shooting Guide
A General Guide
Wire E N L 1 2 3 4 5 6
ASY7-12A Earth Neutral Comp+Fan Unused Unused Unused Unused Unused Unused
ASY7-12R Earth Neutral Comp Unused Unused Rev Valve OD Fan Unused Unused
ASY13PS Earth Neutral Line to OD Unused Unused Signal Unused Unused Unused
ASY14A & ABY14-24A Earth Unused Unused Neutral Comp+Fan Unused Unused Unused Unused
ASY17-30A Earth Unused Unused Live to In Neutral Comp+Fan Unused Unused Unused
ASY14-17R & ABY14R Earth Unused Unused Neutral Comp Rev Valve OD Fan Unused Unused
ASY20-30R & ABY18-24R Earth Unused Unused Neutral Comp Fan Hi Rev Valve Fan Low Unused
AUY12-18AG Earth Unused Unused Neutral Comp Fan Hi Fan Low Unused Unused
AUY12-18RG Earth Unused Unused Neutral Comp Fan Hi Rev Valve Fan Low Unused
AUY18-54A, ABY30-54A & ARY24-60A Earth Unused Unused Comp Neutral Live to In Unused Unused Unused
AUY18-54R, ABY30-54R & ARY24-60R Earth Unused Unused Signal Neutral Live to In Unused Unused Unused
Pipework
Pipesizes and lengths should be as the
relevant Technical Guide
Bothlinesshouldbeinsulated
Nolineaccessoriesoroiltrapsshould
be fitted
Incoolingmodebothpipesshouldbe
between 0 and 10°C - the suction line
should sweat, but not freeze
Inheatingmodedbothpipesshouldbe
between 30 and 60°C
Pipeworkshouldberefrigerationquality
RefrigerantshouldbeR22,unless
stated on the outdoor unit
Lookforrestrictions.Theycouldcause
compressor failures.
Indoor Unit
Isitlevel?Haveweadequatedrainage?
Smellsarealwaysduetositeconditions
or drains
Flashinglights?=FaultDiagnostics–
see over
Whenwerethefilterslastcleaned?
Istheunittoolarge/small
(between 5/20 air circs / hr)
IsitonTimer/TestMode
Outdoor Unit
Dischargetemperatureshouldbe
between 50 & 70°C
Suctiontemperatureshouldbe
between -3 & 4°C
Iffanswitchesoffcheckforhigh
discharge temperature
CheckSuctionLineissweating–
problem if not!
HotRecip.Compressor=PROBLEM!
Sweating/Frostonexpansionline–
undercharged
Controller
EE:EEonLCDhandset–
fault diagnostics – see over
Isthehandsettoofaraway?
Whenwerethebatteries
changedlast?
HeatPumpmodels7-14–
NOT auto changeover
Timerisoneshot,unlessithas
repeat’ mode
Withwiredhandset,check
for interference. Cable should
be screened
IsitonTimer/TestMode
Wiring
Ingeneralinterconnectingwiringis
240 Volt, but see chart for details
WithLCDwiredhandsetmodels,
Terminal 3 is the Live Not Terminal 1
NEVER apply mains voltage to
Terminal 1 on these models
WithLCDwiredhandsetmodels
wiring should be screened
CheckVoltagedrops!Checkitisn’t
down to Earth!
Hasitgotatimeclock/BMS
interface?
InterconnectingcablesMUSTbe
circular crimped