1. Manual Auto Switch failure 2. Controller PCB and Indicator PCB failure
Test 1 : Check the Manual Auto Switch
Check if Manual Auto Switch is kept pressed.
Check ON/OFF switching operation by using a meter.
>> If Manual Auto Switch is disabled (on/off switching), replace it.
Test 2 : Replace Controller PCB and Indicator PCB
If Test 1 do not improve the symptom, replace Controller PCB and Indicator PCB.
Trouble shooting 7
INDOOR UNIT Error Method:
Manual Auto Switch Error
Indoor unit controller PCB
Indicator PCB
When the Manual Auto Switch becomes ON for consecutive
60 seconds or more.
Detective Actuators:
Detective details:
Indicate of Display:
Manual auto switch
Forecast of Cause:
02-11
Indoor Unit
Outdoor Unit
Operation lamp : 3 time Flash
ERROR CODE : [E : 35]
Timer lamp: 5 time Flash
Monitor
ABCDEF
: Light ON : Light OFF n : n time blinking