¢ Drain control for dehumidification operation (For Compact
cassette and Slim duct types)
During cooling or dry mode
When the compressor starts, the drain pump starts simultaneously.
The drain pump operates continuously for 3 minutes after the compressor is turned off.
3 minutes
On
Off
On
Off
Compressor
Drain pump
When the compressor stops by the "Anti-freezing control (cooling and dry mode)" on page 04-
83, the drain pump is turned off in 1 hour after the compressor stops.
When the float switch is on, the compressor, indoor and outdoor fan motor operation are
stopped.
Drain pump operates continuously for 3 minutes after the float switch is turned off and then
drain pump is turned off.
When the float switch turns on continuously for 3 minutes, "failure indication" operates. (It is
necessary to turn off power for release it.)
When the float switch turns off less than 3 minutes, the unit starts cooling operation. Indoor
fan motor starts after the float switch is turned off and the compressor starts after 3 minutes st.
3 minutes
3 minutes ST
On
Off
On
Off
On
Off
On
Off
Float switch
Compressor
Indoor fan
Drain pump
Less than 3 minutes
7-11. Drain pump control - (04-80) - 7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu AUXG07KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AUXG07KVLA and is the answer not in the manual?

Fujitsu AUXG07KVLA Specifications

General IconGeneral
BrandFujitsu
ModelAUXG07KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals