1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
Compressor frequency range
Unit: rps
Model name Minimum frequency Maximum frequency
AUXG30KRLB 15 rps 120 rps
AUXG36KRLB 15 rps 120 rps
AUXG45KRLB 20 rps 120 rps
AUXG54KRLB 17 rps 120 rps
1-2. Heating operation - (04-3) - 1. Compressor frequency control