CIRCUITING GUIDELINES
Loads Per Cable
Close Zone: 0 to 40' (0 to 12.2 m)
12 AWG (2.05 mm): 160 W max. 10 AWG (2.59 mm): 180 W max. 8 AWG (3.26 mm): 220 W max.
Far Zone: 80 to 120' (24.4 to 36.6 m)
12 AWG (2.05 mm): 100 W max. 10 AWG (2.59 mm): 120 W max. 8 AWG (3.26 mm): 180 W max.
Mid Zone: 40 to 80' (12.2 to 24.4 m)
12 AWG (2.05 mm): 120 W max. 10 AWG (2.59 mm): 140 W max. 8 AWG (3.26 mm): 200 W max.
Out There Zone: 120 to 160' (36.6 to 54.9 m)
12 AWG (2.05 mm): 60 W max. 10 AWG (2.59 mm): 100 W max. 8 AWG (3.26 mm): 160 W max.
8
Installing the Luxor Transformer
Running Cable to the Fixtures
Aer you install the transformer and determine all xture
locations, run a correctly sized cable from the transformer to the
xtures. FX Luminaire LED xtures require between 10 and 15 V
for optimal operation and longevity. This is accomplished by the
following:
1. Group xtures into distance zones as illustrated below.
Do not include a xture that is 10' (3 m) away from the
transformer on the same cable run as one that is 100'
(30 m) away.
2. Use the proper cabling method for the application. Center-
load all cable runs to minimize the voltage dierential
between xtures.
3. Use a correctly sized cable to accommodate voltage drop. As
a general best practice, limit the wattage load per cable run
to no more than 160 W.