K
Kathleen ButlerAug 11, 2025
What to do if Galletti MCC compressor does not start?
- JJason JonesAug 12, 2025
If the compressor on your Galletti Air Conditioner isn't starting, it could be due to: * Compressor burnout or seizure: The solution is to replace the compressor. * Compressor contactor de-energized: Check the voltage at both ends of the compressor contactor coil and check the coil's continuity. * Open power circuit: Find the cause that tripped the protection. Look for short circuits in the wiring or windings of the pump, fan, compressor motors, or the transformer. * Motor thermal protection open: The compressor may have operated in critical conditions or there might be insufficient refrigerant. Check the working conditions to ensure they are within operating limits.








