10.5.18 Setting parameters
Order number Code State Default Minumum Maximum
Setting
interval
Unit
1.1 DHW MODE Enable or disable the DHW mode:0=NON,1=YES 1 0 1 1/
1.2 DISINFECT Enable or disable the disinfect mode:0=NON,1=YES 1 0 1 1/
1.3 DHW PRIORITY Enable or disable the DHW priority mode:0=NON,1=YES 1 0 1 1 /
1.4 DHW PUMP Enable or disable the DHW pump mode:0=NON,1=YES 0 0 1 1/
1.5 DHW PRIORITY TIME SET Enable or disable the DHW priority time set:0=NON,1=YES 0 0 1 1 /
1.6 dT5_ON The temperature difference for starting the heat pump 10 1 30 1
1.7 dT1S5 The correct valve to adjust the output of the compressor. 10 5 40 1
1.8 T4DHWMAX
The maximum ambient temperature that the heat pump
can operate at for domestic water heating
43 35 43 1
1.9 T4DHWMIN
The minimum ambient temperature that the heat pump can
operate for domestic water heating
-10 -25 5 1
1.10 t_INTERVAL_DHW the start time interval of the compressor in DHW mode. 5
55 1 MIN
1.11 dT5_TBH_ OFF
the temperature difference between T5 and T5S that
turns the booster heater off.
5 0 10 1
1.12 T4_TBH_ON the highest outdoor temperature the TBH can operate. 5 -5 20 1
1.13 t_TBH_DELAY
the time that the compressor has run before starting the
booster heater
30 0 240 5 MIN
1.14 T5S_DI
the target temperature of water in the domestic hot water
tank in the DISINFECT function.
65 60 70 1
1.15 t_DI_HIGHTEMP.
th
e time that the highest temperature of water in the
domestic hot water tank in the DISINFECT function will
last
15 5 60 5 MIN
1.16 t_DI_MAX the maximum time that disinfection will last 210 90 300 5 MIN
1.17 t_DHWHP_RESTRICT he operation time for the space heating/cooling operation. 30 10 600 5 MIN
1.18 t_DHWHP_MAX
the maximum continuous working period of the heat pump
in DHW PRIORITY mode.
90 10 600 5 MIN
1.20 PUMP RUNNING TIME the
certain time that the DHW pump will keep running for 5 5 120 1 MIN
1.19 DHW PUMP TIME RUN
Enable or disable the DHW pump run as timed and keeps
running f or PUMP RUNNING TIME:0=NON,1=YES
1 0 1 1/
1.21 DHW PUMP DISINFECT
Enable or disable the DHW pump operate when the unit is
in disinfect mode and T5 T5S_DI-2:0=NON,1=YES
1 0 1 1/
2.1 COOL MODE Enable or disable the cooling mode:0=NON,1=YES 1 0 1 1/
2.2 t_T4_FRESH_C
The refresh tim
e of climate related curves for cooling
mode
0.5 0.5 6 0.5 hours
2.3 T4CMAX
The highest ambient operation temperature for cooling
mode
52 35 52 1
2.4 T4CMIN
the lowest ambient operating temperature for cooling
mode
10 -5 25 1
2.5 dT1SC the temperature difference for starting the heat pump(T1) 5 2 10 1
2.6 dTSC the temperature difference for starting the heat pump(Ta) 2 1 10 1
2.8 T1SetC1
The setting temperature 1 of climate related c
urves for
cooling mode.
5
10 5 25 1 MIN
2.9 T1SetC2
The setting temperature 2 of climate related curves for
cooling mode.
16 5 25 1
2.10 T4C1
The ambient temperature 1 of climate related curves for
cooling mode.
35 -5 46 1
2.11 T4C2
The ambient temperature 2 of climate related curves for
cooling mode.
25 -5 46 1
2.12 ZONE1 C-EMISSION
The type of zone1 end for cooling mode0=FCU(fan coil
unit)1=RAD.(radiator)2=FLH(floor heating)
002
1/
2.13 ZONE2 C- EMISSION
The type of zone2 end for cooling mode0=FCU(fan coil
unit)1=RAD.(radiator)2=FLH(floor heating)
0 0 2 1/
The parameters related to this chapter are shown in the table below.
2.7 t_INTERVAL_COOL the start time interval of the compressor in COOL mode 55 1