E
Eric RyanAug 7, 2025
What to do if Gamewell Control Panel SLC devices are not being recognized and a 'Missing' trouble message displays?
- CChristopher MorseAug 7, 2025
If SLC devices aren't being recognized and a 'Missing' trouble message appears, check the hardware connections to ensure the wiring is correct. For the main panel, the positive side of the device must connect to Terminal 34, and the negative side to Terminal 33. For SLC devices, ensure they connect to the SLC loop via the SLC OUT terminals. Also, make sure the SLC devices have been addressed properly and that the correct polarity has been observed for SLC device wiring.