CHV Mini VRF 50/60Hz
88 202105
CHV Mini Series Service
Manual
Capacity (kW) Power Supply
Power Line
(mm2)
Breaker/Fuse (A)
Signal Wire between Indoorand
Outdoor Units (mm)
8/10 220-240V 50Hz/60Hz
3×4.0
40/30
three-core shielded cable 3×1.0
(two-core shielded cable 2×1.0)
12.5/14/16 220-240V 50Hz/60Hz
3×6.0
63/45
12.5/14/16 380-415V 50Hz/60Hz
5×2.5
25/20
8. Electric Characteristics